GE D30 Instruction Manual page 488

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CONTROL ELEMENTS
The D30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
The maximum number of autoreclosure elements available is equal to the number of installed CT banks.
The autoreclosure feature is intended for use with transmission and distribution lines, in three-pole tripping schemes for
single breaker applications. Up to four selectable reclosures "shots" are possible prior to locking out. Each shot has an
independently settable dead time. The protection settings can be changed between shots if required, using FlexLogic.
Logic inputs are available for disabling or blocking the scheme.
Faceplate panel LEDs indicate the state of the autoreclose scheme as follows:
Reclose Enabled — The scheme is enabled and can reclose if initiated
Reclose Disabled — The scheme is disabled
Reclose In Progress — An autoreclosure has been initiated but the breaker has not yet been signaled to close
Reclose Locked Out — The scheme has generated the maximum number of breaker closures allowed and, as the fault
persists, does not close the breaker again; known as "Lockout." The scheme can also be sent in "Lockout" when the
incomplete sequence timer times out or when a block signal occurs while in "reclose in progress." The scheme must be
5
reset from Lockout in order to perform reclose for further faults.
The reclosure scheme is considered enabled when all of the following conditions are true:
The
AR1 FUNCTION
The scheme is not in the "Lockout" state
The "Block" input is not asserted
The
AR1 BLK TIME UPON MNL CLS
The autoreclose scheme is initiated by a trip signal from any selected protection feature operand. The scheme is initiated
provided the circuit breaker is in the closed state before protection operation.
The reclose-in-progress (RIP) is set when a reclosing cycle begins following a reclose initiate signal. Once the cycle is
successfully initiated, the RIP signal seals-in and the scheme continues through its sequence until one of the following
conditions is satisfied:
The close signal is issued when the dead timer times out, or
The scheme goes to lockout
While RIP is active, the scheme checks that the breaker is open and the shot number is below the limit, and then begins
measuring the dead time.
Each of the four possible shots has an independently settable dead time. Two additional timers can be used to increase the
initial set dead times 1 to 4 by a delay equal to
selected settings. This offers enhanced setting flexibility using FlexLogic operands to turn the two additional timers "on"
and "off." These operands can possibly include
up to maximum 4 selectable shots. Maximum number of shots can be dynamically modified through the settings
REDUCE MAX TO 1 (2, 3)
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs:
The maximum shot number was reached
A "Block" input is in effect (for instance, Breaker Failure or bus differential protection operated)
The "Incomplete Sequence" timer times out
5-278
AR1 RESET TIME:
60.000 s
AR1 INCOMPLETE SEQ
TIME: 5.000 s
AR1 EVENTS:
Disabled
is set to "Enabled"
timer is not active
AR1 DELAY 1
AR1 SHOT CNT
, using the appropriate FlexLogic operand.
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: Disabled, Enabled
or
or the sum of these two delays depending on the
AR1 DELAY 2
1, and so on. The autoreclose provides
=n,
SETTING GROUP ACT
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
AR1

Advertisement

Table of Contents
loading

Table of Contents