Front Panel Labelling - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
User-programmable event-cause indicators
Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as "Self-Reset" or "Latched." If set to "Self-Reset," then the corresponding event cause LED remains
on as long as the operand associated with the element remains asserted. If set to "Latched" and asserted, then it remains
on until the operand is reset and then a reset command initiated.
All elements that are able to discriminate faulted phases can independently turn on or off the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
The LEDs have defaults and can be configured to show instead the status of any FlexLogic operand.
The labelling area has a clear cover for custom labels. A utility is available to print stick-on labels, as outlined later in this
chapter.
These LEDs are programmed by default as follows:
PICKUP — LED 6 — Indicates that an element is picked up, and hence a trip can be imminent
VOLTAGE — LED 7 — Indicates voltage was involved
CURRENT — LED 8 — Indicates current was involved
FREQUENCY — LED 9 — Indicates frequency was involved
OTHER — LED 10 — Indicates a composite function was involved
PHASE A — LED 11 — Indicates phase A was involved
PHASE B — LED 12 — Indicates phase B was involved
PHASE C — LED 13 — Indicates phase C was involved
NEUTRAL/GROUND — LED 14 — Indicates that neutral or ground was involved

4.2.5 Front panel labelling

4.2.5.1 Enhanced front panes
The following procedure requires these pre-requisites:
The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded from
http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc
Small-bladed knife
To create custom LED and pushbuttons labels for the enhanced front panel:
1.
Start the EnerVista UR Setup software.
2.
If not already copied to the Offline Window area, right-click the online device and select the Add Device to Offline
Window option. Click the Receive button in the window that opens to save the settings file to the Offline Window area.
3.
Type labels as follows. Select the File > Front Panel Report. The window opens.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
FRONT PANEL INTERFACE
and printed
4
4-43

Advertisement

Table of Contents
loading

Table of Contents