5.4.2 Mixed air chamber

Mixed air chamber in sequential operation
The mixed air chamber is controlled from the Y2 output which can be adapted to the dynam-
ics of the mixed air chamber by means of the parameters K
air chamber and T
v
tees an minimum proportion of outdoor air. The operating action of the control output Y2
can be reversed. The default setting is an outdoor air rate of 0 to 100 % which corresponds
to a control signal of 0 to 10 V. By activating Fb22, the operating action is reversed: the out-
door air rate 0 to 100 % then corresponds to 10 to 0 V. On feedforwarding the outdoor
temperature, the summer time operation function is taken into account (–> section 6.10.3).
By additionally feedforwarding the exhaust air temperature, the automatic reversal of the
operating action takes effect.
If the operating action of the control output Y2 is automatically reversed due to changing
temperatures, while the control is in the sequence range Y1 or Y3, the mixed air chamber is
then reversed with a constant changing rate of 15 % per minute. If there is a considerable
difference in temperature between exhaust air and extract air due to the heat given off by
the fan, the extract air temperature can also be selected as the measured variable in place of
the exhaust air temperature.
Note:
The proportion of outdoor air can be suppressed during the warm-up phase with Fb43 = ON.
Functions
Sensor F7, mixed air or extract air
temperature
Operating action Y2
Circ. air mode after system start-up
WE
Configuration
OFF
Fb21
WE
Range of values
0.5
0.1 to 99.9
60 sec 1 to 999 sec
– – –
– – – to 999 sec
Mixed air chamber. The parameter Minimum outdoor air rate guaran-
WE
OFF
OFF
Control methods and system components
Mixed air chamber , T
p
Configuration
Fb7 = ON, option: SEQ (with extract air sensor)
Fb7 = OFF, option: SEQ (without extract air sensor)
Fb22
Fb43 (not with supply air control)
Mixed
N
45
EB 5477 EN