12.6 Customer data

Station
Operator
Responsible Samson office
System code number
Function block settings
Fb
ON/ OFF
1
2
3
4
5
6
7
8
9
10
11
12
OFF
ON
13
Options selected, function block parameters
Mixed air temperature control
Operation in sequence with extract air temperature;
Operation in sequence with exhaust air temperature
Outdoor temperature-compensated mixed air chamber operation
Enable night purge (START): [24] °C
Finish night purge (STOP): [18] °C
Temperature difference to outdoor temperature: [5] °C
Speed 2: BA2 = BA3 = ON or BA2 = OFF, BA3 = ON
Delay time: [0] sec
Enable chiller at outdoor temperature (START): [18] °C
SEQ
Activating value (START): [30] %;
Deactivating value (STOP): [10] %
PAr
Minimum deactivation time (STOP MIN): [600] sec;
Minimum activation time (START MIN): [600] sec;
Cooling deactivated when Y1 > (STOP): [50] %