Eaton Freedom 2100 Installation And Maintenance Manual page 12

Motor control center
Table of Contents

Advertisement

accept the blade of an electrician's screwdriver used to
cam the block into and out of engagement. Each male
Fig. 15 Unit Terminal Blocks
portion also has a rear slot that can engage the edge o
the unit frame where it can be mounted for ease in trou-
ble-shooting.
I.B. 8926-1
NEMA TYPE C WIRING
Each control unit is factory assembled with device
interwired within the unit. In addition, all control wiring i
carried to unit terminal blocks on the side of the unit and
from these unit blocks, along with load wiring through
Size 3, to master terminal blocks located at the top o
bottom of the structure. See Figure 16. Master terminal
blocks can be either fixed or drawout mounted. In the
drawout design the terminal blocks are rack mounted t
permit withdrawal of the entire assembly for ease o wir-
ing during installation and maintenance. Bring field wir-
ing from the horizontal wireway to the master terminal
blocks except for load wiring larger than Size 3. These
latter load wires should be carried into the vertical
wireway and under the bottom right-hand side of the uni
to terminations within the unit.
Fig. 16 Master Terminal Blocks
- Page 12 -