Eaton Freedom 2100 Installation And Maintenance Manual page 19

Motor control center
Table of Contents

Advertisement

NEMA SIZE 5
HEATER PACK SELECTION TABLE
MOTOR FLA RATING
FLA DIAL POSITIONS
A
B
34
41
49
59
72
87
103
107
130
152
129
156
182
194
234
274
MAXIMUM RATINGS
NEMA Size 5 = 270 Amperes Min. Wire Size - 2 AWG
NEMA SIZE 6
HEATER PACK SELECTION TABLE
MOTOR FLA RATING
FLA DIAL POSITIONS
A
B
144
174
205
215
259
304
258
312
365
388
468
547
MAXIMUM RATINGS
NEMA Size 6 = 540 Amperes
FLA rating marked on heater pack multiplied by a
transfomation ratio. For motor FLA values not listed, turn
the dial clockwise for higher or counterclockwise for lower
ratings.
Magnetic Reduced Voltage Starter Classes F600,
F700, F890 with C306 Thermal Overload Relay.
Multiply actual motor
full load current by
factor below and refer
to adjusted full load
current column in
Starter Type
Class
tables.
Autotransformer F600
Part-Winding
F700
Star-Delta
F890
STD
TRIP
CLASS
20
C
D
48
54
H2003B
69
79
H2004B
118
H2005B
174
H2006B
209
H2007B
H2008B
STD
TRIP
CLASS
20
C
D
235
H2005B
348
H2006B
419
H2007B
H2008B
Qty. of
heaters
required
per
starter
1
3
.5
6
.575
3
- Page 19 -
I.B. 8926-1

Advertisement

Table of Contents
loading

Table of Contents