5.1.3 Setting commissioning parameters

To set the commissioning parameters, the heating technician
must be logged into the controller.
Technician login
Configuration
Setup
System Configuration
Setup
Language
Date
Setup
Keylock Function
Access Rights
Outdoor type
Access Rights
Fig. 5-1
Entering the technician code
Set the required commissioning parameters. The enclosed
"Commissioning check list" must be observed and completed
for this.
– Explanation of the operating parameters, see control-
ler operating instructions.
– Enter the set values in the corresponding tables in the
"Notes" chapter of the controller operating instructions.
Activate the Legionella protection (parameter [Anti-Legionella
day]) if required.
If an outside temperature sensor is connected, set the
parameter [Tamb Config] to "1".
Set further commissioning parameters on the ROTEX HPSU
monobloc compact controller depending on system require-
ments.
With glycol in the system, set the parameter [Glycol] to "1".
36
Access Rights
Access Rights
User
Access Rights
Expert
Access Rights
Configuration
Setup
System Configuration
System Configuration
Power DHW
BUH s1 power
Fig. 5-2
Setting the commissioning parameters

5.1.4 Bleeding the hydraulic system

If the storage tank temperature falls below specific
minimum values, the ROTEX HPSU monobloc
compact's safety settings prevent the heat pump from
being operated at low outside temperatures:
– Outside temperature < -2 °C, minimum storage tank
temperature = 30 °C
– Outside temperature < 12 °C, minimum storage tank
temperature = 23 °C.
Without backup heater:
The storage tank water must be heated to the required mini-
mum storage tank temperature with an external heater booster.
With backup heater (BUxx):
At an outside temperature of < 12 °C and a storage tank tem-
perature of < 35 °C, the backup heater (BUxx) is automatically
switched on to heat the storage tank water to at least 35 °C.
To speed up the heating process with backup heater,
temporarily set
– parameter [Function Heating Rod] = "1" and
– parameter [Power DHW] to the maximum value of the
backup heater.
– Set the rotary switch to
the parameter [1x Hot Water] to "On". After heating, set
the parameter to "Off" again.
FA ROTEX HPSU monobloc compact • 09/2017
Setup
Language
Date