4Cabling Of The Digital Output Contacts To Monitor Other Inverter Operation Modes Than Warnings And Alarms; Cabling Of Main/Auxiliary Control Functionality - ABB ESI-S Installation, Operation And Maintenance Instructions

Energy storage inverter 1ph
Table of Contents

Advertisement

outputs of the ESI-Manager have been set up for monitoring other functions than
warnings (cf.
Table
conditions and how to associate them with digital output contacts.
For cabling the digital output contacts as warning contact, the same approach as shown
in
Figure 44
can be adopted. The electrical characteristics of the digital output contacts
and the points to pay attention to are discussed in
6.13.4 Cabling of the digital output contacts to monitor other inverter operation
modes than warnings and alarms
Table 9
gives an overview of the other functions that can be monitored with the digital
outputs in addition to the already discussed warnings and alarms.
For cabling the digital output contacts to monitor other inverter operation, the same
approach as shown in
digital output contacts and the points to pay attention to are discussed in

6.13.5 Cabling of main/auxiliary control functionality

The active inverter features main and auxiliary control setup modes. This implies that
two different compensation characteristics can be defined, e.g. one for the day and one
for the night or one for normal network operation and one for backup generator
operation. With the ESI-Manager a set up can be made to either use always the main or
the auxiliary settings. In addition, the possibility exists to switch between main and
auxiliary settings 'automatically' according to a signal applied to a digital input of the
ESI-Manager (Cf.
factor for switching between the main and auxiliary settings. Moreover, both normal and
inverse logic can be used to drive the digital inputs.
The electrical requirements of the digital inputs are as discussed in
Figure 45
gives an example of how to implement the main/auxiliary control switching
functionality on Digital Input 2. It is assumed that normal control logic is used.
24 Vdc
external
supply
-
Remark:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
Figure 45: Example of how to cable the 2
10) Refer to
Section 7.9.2.4.1
Figure 44
can be adopted. The electrical characteristics of the
Figure
40). Any digital input can be configured to act as the deciding
+
External switch for
switching between main
and auxiliary filter settings
control switching functionality
Manual Energy Storage Inverter ESI-S ç Electrical design and installation 63
for guidelines on how to set up warning
Section
ESI-Manager
3
(a)
4
(a)
nd
digital input of the ESI-Manager for main/auxiliary
6.13.2.
Section 6.13.2.
Chapter 6.
Digital input 2
(15-24Vdc)