Other Component Specifications - Panasonic S-200PE2E5 Technical Data & Service Manual

Dc inverters
Table of Contents

Advertisement

1

1-3. Other Component Specifications

Outdoor Units U-200PE2E8A
MODEL No.
Power Transformer
Rated
Source
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
Thermistor (Discharge gas sensor): TH5
Resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 20°C)
Sol-Control-Valve
Sol-control-valve
Magnetic coil
4 way valve
4 way valve
Electro magnetic coil
AMP Air Conditioning
Outdoor Unit
VAC, Hz
kΩ
kΩ
VAC
VAC, A
1-12
U-200PE2E8A
-20°C: 38.48±2%     20°C: 6.517±2%
-10°C: 23.67±2%     30°C: 4.448±2%
0°C: 15.00±2%     40°C: 3.100±2%
5°C: 12.06±2%     45°C: 2.607±2%
10°C: 9.765±2%     50°C: 2.203±2%
60°C: 1.593±2%      85°C: 0.7598±2%
65°C: 1.363±2%      90°C: 0.6623±2%
70°C: 1.171±2%      95°C: 0.5793±2%
75°C: 1.010±2%     100°C: 0.5083±2%
80°C: 0.8746±2%  
UKV32D322
UKV-A392
SHF-20B-46-DC
SQ-D23015-002283 DC15.4V(898mA)
www.ampair.co.uk | sales@ampair.co.uk
 105°C: 0.4473±2%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-250pe2e5U-250pe2e8aS-100pu2e5aS-125pu2e5aU-200pe2e8a

Table of Contents