5. TRANSPORT AND INSTALL THE OUTDOOR UNIT

Transporting
1. Transport the outdoor unit in its original packaging as close as possible to the installation
location.
2. In the event that the unit needs to be lifted or suspended, use a rope or belt and use
cloth or wood as padding to avoid damaging the unit.
3. Use the side handles to carry the unit and be careful not to touch the fi n with your hand
or any objects.
Installation
1. Read the "Select the outdoor unit installation location" thoroughly before installing the
outdoor unit.
2. When installing to a concrete or solid surface, use M10 or a W 3/8 bolts and nuts to
secure the unit. Ensure that it installed upright on a horizontal plane. (Use an anchor
bolt for the installation as shown in the diagram below.)
3. Avoid installing on the slanted roof.
4. In the even where the roof is at risk of receiving oscillations or vibrations, secure the unit
with a seismic isolating mount or vibration absorbing rubber.
5. The drain water will be discharged from the unit during heating or
defrosting operation mode.
Select an appropriate location with good drainage system. (In the
winter, there is risk of slipping due to freezing, and depending on the
installation set up there is risk of drain water running overhead.)
*
Please consult us if installing drain elbows.
*
In cold regions (where the outdoor temperature can drop to below
0˚ for 2 to 3 consecutive days), the drain water may freeze and
may prevent the fan from operating. For this case, do not use the
drain elbow.
AMP Air Conditioning
230
159
1-42
www.ampair.co.uk | sales@ampair.co.uk
More than 40mm
Base
Anchor bolt length
(Unit: mm)
200
160
350
660
159
(Anchor pitch)
Drain hole ø32