10. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
 Models: ARGA30FMTA, ARGA36FMTA, and ARGA45FMTA
Connector
CN102
Control input
CN103
CN6
 Model: ARGA60FHTA
Connector
CN46
Control input
* CN47
*: Any one of the output functions can be selected by function setting No.60.
10-1. Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial on/
off switch to a connector on the external control PCB and turning it on.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
 Circuit diagram example
Indoor unit
control PCB
24 V
Connector
1
3
• When function setting is in "Operation/Stop" mode
Input
Operation status output
Fresh-air control output
Input
Operation status output
Error status output
Fresh-air control output
Initial setting after power is on
Auto changeover
24 °C
AUTO
Standard air direction (swing OFF)
• Contact capacity: DC 24 V or more, 10 mA or more.
Connected unit
• *: Make the distance from the PCB to the connected
Example: Switch
• Use non-polar relays and switches.
*10 m
Signal
Locally purchased
- 34 -
Output
Output
Starting mode other than initial
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
unit within 10 m.
Remarks
See external input/output
settings for details.
Remarks
See external input/output
settings for details.
setting