 Outdoor unit installation in multi-row
Single parallel unit arrangement
600 or more
1,500 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no
obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
Multiple parallel unit arrangement
500 or more
3,000 or more
- 57 -
600 or more
1,500 or more
150
250 or more
1,500 or more
Unit: mm
500 or more
3,500 or more
500 or more