Fujitsu ARGA18FMTA Design & Technical Manual page 30

Table of Contents

Advertisement

(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops
flashing. If the setting value indicator changes or if "- -" is displayed when the flashing stops, the setting value has not been set
correctly. (A disable setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons (
more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1
minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS OF FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition.
After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if inenable numbers or setting values are selected.
1)
2)
3)
4)
5)
6)
7)
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the
room.
If the indication is not required, select "No indication" (03).
Function Number
11
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function Number
21
Refer to "7. FAN PERFORMANCE AND CAPACITY".
3) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
Function Number
30
!
CAUTION
Filter sign
Static pressure
Room temperature sensor control for cooling
Auto restart
Room temperature sensor switching
External input control
Room temperature sensor switching (Aux.)
Setting Value
Setting Description
00
Standard (2500 hours)
Long interval (4400 hours)
01
Short interval (1250 hours)
02
03
Setting Value
Setting Description
00
01
High static pressure 1
02
High static pressure 2
03
High static pressure 3
Setting Value
Setting Description
00
01
02
Slightly higher control
03
- (01 - 27) -
) and FAN button simultaneously again for
) (
(  . . .Factory setting)
No indication
(  . . .Factory setting)
Normal
(  . . .Factory setting)
Standard
Lower control
Higher control

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoga25fbtahArga25fmtaAoga18fbtah