 Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function no.
1)
11
2)
21
3)
30
4)
40
5)
42
6)
46
7)
48
8)
60
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
11
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
For 30 model
Function number
21
For 36, 45 model
Function number
21
For 60 model
Function number
21
Filter sign
Static pressure
Room temperature sensor control for cooling
Auto restart
Room temperature sensor switching
External input control
Room temperature sensor switching (Aux.)
Switching functions for external output terminal
Setting value
00
01
02
03
Setting value
00
01
02
03
Setting value
00
01
02
03
Setting value
00
02
03
04
- 45 -
Functions
Setting description
Standard (2,500 hours)
Long interval (4,400 hours)
Short interval (1,250 hours)
No indication
Setting description
Normal (30 Pa)
High static pressure 1 (60 Pa)
High static pressure 2 (90 Pa)
High static pressure 3 (120 Pa)
Setting description
Normal (60 Pa)
Low static pressure (30 Pa)
High static pressure 1 (90 Pa)
High static pressure 2 (120 Pa)
Setting description
Normal (60P a)
High static pressure 1 (100 Pa)
High static pressure 2 (130 Pa)
High static pressure 3 (160 Pa)
Factory setting
Factory setting
Factory setting
Factory setting