2-3. Installation space requirement
Provide sufficient installation space for product safety.
 Model: AOGA30FBTAS
 Single outdoor unit installation
• When the upper space is open:
When there are obstacles at the rear only.
When there are obstacles at the front only.
• When there is an obstruction in the upper space:
When there are obstacles at the rear and
above.
Max. 500
When there are obstacles at the rear and sides.
150 or more
When there are obstacles at the front and rear.
1,000 or more
When there are obstacles at the rear, sides, and
above.
1,000
or more
300
or more
250 or more
- 55 -
200
or more
200
or more
1,000 or more
Max. 500
250 or more
Unit: mm
300
or more
150 or more
Unit: mm
1,500 or more
500 or more

Hide quick links: