ECR International CHB Application Manual page 41

Wall mounted gas boiler
Table of Contents

Advertisement

Figure 5 - Low Voltage Terminal Strip, CHB-130
Shown
Check our website frequently for updates: www.ecrinternational.com
DOMESTIC HOT WATER SENSOR KIT
Low Voltage
Terminal Strip
Temperature Deg F
32
60
70
77
100
110
120
130
Figure 6 - Low Voltage Terminal Strip Removed from
Boiler, CHB -130 Shown
Low Voltage
Terminal Strip
Resistance in Ohms
32505
15689
11935
10000
8060
4732
3748
3104
41
Removed
P/N 240010745 Rev. D [08/31/2015]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

CcbChb 150Chb 100Chb 130Ccb 150

Table of Contents