Single Quinta Pro boiler, heating only with low loss header
(Time and temperature control by others)
Power Supply
•
Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
•
Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
•
Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
•
Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
•
Boiler will recognise the type of control being used
•
Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
•
Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF- 01.
Control option based on temperature or output can be adjusted on the jumper on the IF- 01.
(See installation manual for full details)
•
Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02
max 400Va (1.5 amp). Connect the shunt pump SH1 to the pump fly lead supplied with the
boiler to plug X81