Quinta pro series. suggested shematics with control and power wiring details

Advertisement

Single Quinta Pro boiler, heating only with low loss header
(Time and temperature control by others)
Power Supply
Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
Boiler will recognise the type of control being used
Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF- 01.
Control option based on temperature or output can be adjusted on the jumper on the IF- 01.
(See installation manual for full details)
Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02
max 400Va (1.5 amp). Connect the shunt pump SH1 to the pump fly lead supplied with the
boiler to plug X81