Single Quinta Pro boiler, heating with hot water priority, heating
room or weather compensated with the iSense controller
(Optimising/Weather compensated heating with timed hot water)
Power Supply
Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
Boiler will recognise the type of control setting used
Fit the control in a normally occupied reference room within the building being heated.
Refer to the instructions supplied with the control package
Set up the controller to suit the design requirements and occupancy times for heating and
hot water in accordance with the instruction documents supplied with the controller
Install the outside sensor on a North facing wall in a sheltered position and connect to
terminals 'Tout' on the main PCB of the boiler
DHW Control
Diverting valve option:
Connect valve to the terminals shown, connect shunt pump PM1 to the terminals shown.
Connect valve ports AB, A and B as shown (AB = boiler, A = hot water, B = heating)
Primary Pump option:
Connect pump PM1 to the terminals shown
Connect shunt pump to the terminals shown
Note: This option will only operate with a calorifier sensor. This is to allow the iSense to control
the hot water times.