Front Panel Controls
Power On/Off
Test
Load Level LED Gauge
Battery Charge LED Gauge
Voltage Manager Boost LED
Voltage Output On LED
Voltage Manager Buck LED
On Battery LED
Replace Battery LED
Overload LED
Fault Code LED
System Over Temperature LED
Rear Panel Information and Controls
Configuration Manager DIP Switches
Communications Manager DB9 Port, USB Port
Circuit Breaker
AC Inlet Module
SNMP Slot (Contact Factory)
Internal Batteries
User Hot-Swappable (See Instruction Manual)
Type: 12 Volt, High Rate 23W
Quantity: 8 Batteries
Recharge Time: 8 Hours to 80%, 24 Hours to Full Charge
Environmental
0
Temperature: 0 - +40
-20 to 60
Storage
Internal Batteries Only
Internal + 1) E4804-12
Internal + 2) E4804-12
Internal + 3) E4804-12
Internal + 4) E4804-12
Internal + 5) E4804-12
Internal + 6) E4804-12
Internal + 7) E4804-12
Internal + 8) E4804-12
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode
at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-
NM, CM-CM, NM-COM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A -
6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support: POWERVAR warrants the electronics and transformers used in its uninterruptible power managers to be free from
defects in materials and workmanship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from
the date of shipment. For service or support on any POWERVAR product, please contact POWERVAR Technical Support at (800) 369-7179 or
visit the POWERVAR website at ww.powervar.com.
Battery Life Disclaimer: POWERVAR's standard battery warranty applies only to UPS and UPM products which are continuously connected to
AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will
experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products
used in such applications will experience substantially reduced battery life. For that reason, POWERVAR's standard battery warranty does not
apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. POWERVAR UPS and
UPM products used in such applications shall receive a 90 day warranty on batteries.
A03-00465 - Rev. C
A01-00104 Rev A
Security II UPM Specifications
North American Models ABCE2202-11R
0
C (32 to 104
F) Operating
0
0
C (-40 to 140
F) Shipment/
2200VA UNIT DERATED 1800VA TYPICAL RUN-TIMES (MINs)
10%
20%
30%
(162W)
(324W)
(486W)
105
60
38
395
180
113
685
300
188
975
420
263
1265
540
338
1555
660
413
1845
780
488
2135
900
563
2425
1020
638
Humidity:
5 to 90% Non-Condensing (Operating,
Shipment/Storage)
Altitude:
3,000m (10,000 ft) max. Operating;
12,000m (40,000 ft) max. Shipment/Storage.
Safety Agency and EMC Compliance:
All Units are Listed by UL and Marked with the UL/cUL Marking.
Standard UPM:
Products Listed To:
UL1778 5th Edition
CSA 22.2 Nos. 107.3-14
Products in compliance with:
FCC-Part 15, Subpart B, Sections 15.107b & 15.109b
Class A Digital Device*
CISPR11:2009, A1; 2010, Class A*
IEC61000-4-2, Electrostatic Discharge
IEC61000-4-3, Radiated Electromagnetic Field Immunity
IEC61000-4-4, Electrical Fast Transient/Burst Immunity
IEC61000-4-5, Surge Immunity
IEC61000-4-6, Immunity to Conducted Radio Frequency
Disturbances
IEC61000-4-8, Power Frequency Magnetic Field Immunity
IEC61000-4-11, Voltage Dips, Short Interruptions, and
Voltage Variations
*Note: Class B is Available as an Option
Please Consult Your Powervar Sales Representative
RoHS Compliance:
All Products (Standard and Medical) are RoHS Compliant
40%
50%
60%
(648W)
(810W)
(972W)
25
16
14
70
56
43
115
96
72
160
136
101
205
176
130
250
216
159
295
256
188
340
296
217
385
336
246
2
70%
80%
90%
(1134W)
(1296W)
(1458W)
10
9
7.5
32
26
21.5
54
43
35.5
76
60
49.5
98
77
63.5
120
94
77.5
142
111
91.5
164
128
105.5
186
145
119.5
100%
(1620W)
5.5
17.5
29.5
41.5
53.5
65.5
77.5
89.5
101.5