A. Fuel Conversion - Outdoor Lifestyles ODMEZG-36 Installation Manual

Mezzanine series
Table of Contents

Advertisement

9
Gas Information

A. Fuel Conversion

• Make sure the appliance is compatible with available gas
types.
• Conversions must be made by a qualified service
technician using Hearth & Home Technologies specified
and approved parts.
B. Gas Pressure
• Optimum appliance performance requires proper input
pressures.
• Gas line sizing requirements will be determined in ANSI
Z223.1 National Fuel Gas Code in the USA and CAN/
CGA B149 in Canada.
• Pressure requirements are:
Gas Pressure
Minimum inlet pressure
Maximum inlet pressure
Manifold pressure
WARNING! Risk of Fire or Explosion! High pressure
will damage valve. Low pressure could cause explosion.
• Verify inlet pressures. Verify minimum pressures when
other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is
greater than 1/2 psig.
• Valve pressure taps are accessible by removing the
barrier screen. See Figures 9.1 & 9.2.
VALVE PRESSURE TAPS
Figure 9.1. Valve Pressure Taps.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
40
Natural Gas
Propane
5.0 in. w.c.
11.0 in. w.c.
10.0 in. w.c.
13.0 in. w.c.
3.5 in. w.c.
10.0 in. w.c.
Outdoor Lifestyles • ODMEZG-36 Installation Manual • 4601-901 Rev. B • 10/17
Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI 223.1. Installation
should be done by a qualified installer approved and/or
licensed as required by the locality. (In the Commonwealth
of Massachusetts installation must be performed by a
licensed plumber or gas fitter).
Note: A listed (and Commonwealth of Massachusetts ap-
proved) 1/2 in. (13 mm) T-handle manual shut-off valve
and flexible gas connector are connected to the 1/2 in. (13
mm) control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
C. Gas Service Access
Note: This appliance does include a manual gas shutoff
valve that is located in the valve compartment. This manual
gas shutoff valve is accessible for service by removing
the barrier screen. See Figure 9.2. The valve is most
accessible if it is located forward in the control cavity of
the appliance.
Depending upon local code, an additional manual gas
shutoff, in a readily accessible area may be required and
located upstream from the appliance.
Figure 9.2 Gas and Electrical Access - Remove Glass Window

Advertisement

Table of Contents
loading

Table of Contents