I. Measuring Standards

Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards:
• Pipe measurements are shown using the effective length
of pipe. See Section 11.A for information on effective
length of pipe components.
• Horizontal terminations are measured to the outside
mounting surface (flange of termination cap) (see Figure
5.15).
• Vertical terminations are measured to top of last section
of pipe. See Figure 5.16.
• Horizontal pipe installed level with no rise.
Figure 5.15 Measure to Outside Mounting Surface
Figure 5.16 Measure to Top of Last Section of Pipe
24
MEASURE TO SHADED SURFACE
(OUTSIDE MOUNTING SURFACE)
Outdoor Lifestyles • ODMEZG-36 Installation Manual • 4601-901 Rev. B • 10/17
J. Vent Diagrams
General Rules:
• When penetrating a combustible wall, a wall shield
firestop must be installed.
• When penetrating a combustible ceiling, a ceiling firestop
must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
• Horizontal termination cap should have a 1/4 inch
downward slant to allow any moisture in cap to be
released. See Figure 5.17.
1/4 in. max.
(6 mm)
Figure 5.17