Gas Pressure - Rheem 97MDV060 Series Installation Instructions Manual

(-)97v series upflow condensing modulating, communicating gas furnaces w/ecm blower (-)97v series
Table of Contents

Advertisement

GAS SUPPLY

GAS PRESSURE

IMPORTANT: Do not run a flexible gas connector inside
the furnace. The gas pipe gasket in the cabinet does not
seal around a flexible gas line.
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use
a connector which has previously serviced another gas
appliance. Massachusetts law requires that all flexible
connectors be less than 36".
It is important to have all openings in the cabinet
burner compartment sealed for proper furnace opera-
tion.
IMPORTANT: ENSURE that the furnace gas valve is not
to be subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual manual gas
stop from the gas supply piping during any pressure test-
ing that exceeds 1/2 PSIG. (3.48 kPa).
Natural gas supply pressure must be 5" to 10.5" w.c.
LP gas supply pressure must be 11" to 13" w.c. This
pressure must be maintained with all other gas-fired
appliances in operation.
The minimum gas supply pressure to the gas valve for
proper furnace input adjustments is 5" w.c. for natural gas,
however 6" to 7" is recommended. The minimum gas sup-
ply pressure is 11" w.c. for LP gas.
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE
FURNACE INPUT RATING BE ADJUSTED AND THAT
THE SIZE OF THE BURNER ORIFICES BE RECAL-
CULATED BASED ON ELEVATION AND GAS HEAT-
ING VALUE. THE BURNER ORIFICES MAY (OR MAY
NOT) NEED TO BE CHANGED. SEE THE SECTION
TITLED "HIGH ALTITUDE INSTALLATIONS" OF THIS
BOOK FOR INSTRUCTIONS.
46
TABLE 11
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
gravity of 0.60 (natural gas).
Nominal
Iron Pipe
Size, Inches
10
20
1/2
132
92
3/4
278
190
1
520
350
1-1/4
1,050
730
1-1/2
1,600
1,100
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT
termined by consulting the local natural gas utility or the LP gas supplier.
FIGURE 31
ST-A1194-88-00
FIGURE 32
OFF/ON SWITCH
Length of Pipe, Feet
30
40
50
60
73
63
56
50
152
130
115
105
285
245
215
195
590
500
440
400
890
760
670
610
Gas Input of Furnace (BTU/HR)
=
Heating Value of Gas (BTU/FT
OUTLET / MANIFOLD TAP
LP JUMPER WELL
ST-A1194-88-00
(INSERT JUMPER HERE)
ADJUSTMENT WELL
SUPPLY PRESSURE TAP
ST-A1194-89-00
70
80
46
43
96
90
180
170
370
350
560
530
3
)
3
) may be de-
ST-A1194-89-00