GENERAL VENTING REQUIREMENTS AND
VENT PIPE SIZING AND MAXIMUM VENT LENGTHS (cont.)
POLYPROPYLENE VENT PRODUCTS
Centrotherm brand Innoflue and Duravent Polypro Single-
wall and flex venting products are approved for use on this
furnace product only in single appliance applications. Do
bows listed in these instructions (Vent Pipe Sizing and
not exceed maximum venting lengths, diameters or el-
Maximum Vent Lengths section [Table 3]). Application of
these products is limited to the terminations listed in Ta-
T BLE 4: DUR VENT BR ND POLYPRO & POLYPRO FLEX
TERMIN TION COMPONENTS
T BLE 5: CENTROTHERM BR ND ECO SYSTEMS TERMIN TION COMPONENTS
GUIDELINES
bles 4 and 5 below. These manufacturers have provisions
for B-vent liners and chimney liners which can be used
with this furnace with non-direct venting applications only.
Refer to the manufacturer's installation instructions for
proper installation. Contact the manufacturer for all instal-
lation and application information.
NOTE: These venting products are listed for use in
Canada under ULC-S636.