Download Print this page

Siemens RVP550 Installation Instructions Manual page 3

Energy manager / heating controller
Hide thumbs Also See for RVP550:

Advertisement

Connection diagrams
Markings of connection terminal on the low-voltage side
Termi-
Terminals
nal
M
Ground
Ux
Output DC 0...10 V
P1
PWM output
B109
Temperature sensor
M
Ground sensors
B108
Temperature sensor
B107
Temperature sensor
B106
Temperature sensor
M
Ground sensors
B105
Temperature sensor
Markings of connection terminal on the mains voltage side
Termi-
Terminals
nal
Q110
Multifunctional output
Q109
Multifunctional output
F3
Phase Q109 / Q110
F7
Phase Q108
Q108
Multifunctional output
Q107
Multifunctional output
F6
Phase Q107
Q106
Multifunctional output
Q105
Multifunctional output
F2
Phase Q105 / Q106
Electrical connections
N
Siemens Building Technologies / HVAC Products
N
Termi-
Terminals
nal
H1
Input H1 (contact or DC 0...10 V)
B104
Temperature sensor
B103
Temperature sensor
M
Ground sensors
B102
Temperature sensor
B101
Temperature sensor NTC / LG-Ni 1000
with automatic identification
MD
Ground PPS (room unit, BMU)
A6
Data PPS (room unit, BMU)
MB
Ground bus (LPB)
DB
Data bus (LPB)
Termi-
Terminals
nal
Q104
Multifunctional output
Q103
Multifunctional output
F1
Phase Q103 / Q104
E1
AC 230 V input
Q102
Multifunctional output
F5
Phase Q102
Q101
Multifunctional output
F4
Phase Q101
L
Live conductor AC 230 V
N
Neutral conductor
LPB
D1
D2
74 319 0312 0 a
19.08.2002
3/28

Advertisement

loading

This manual is also suitable for:

Rvp540