Line
Function
202
Display of configuration errors
No display = no error
1-10 = terminals Q101 - Q110 used beyond capacity
11-19 = terminals B101 - B109 used beyond capacity
24 = B73, Y15 or Y¯15 missing
26 = B43, Y14 or Y¯14 missing
33 = B62 incompatible with partial diagram "Solar"
34 = d.h.w. heating BMU incompatible with partial diagram "D.h.w. /
combi storage tank"
38 = external heat source incompatible with partial diagram "Oil / gas"
39 = inadmissible reduction B72
40 = B13 or K18 / K¯18 missing
41 = B8 missing for function with K17
42 = Q17 incompatible with partial diagram "Heat pump"
43 = Q¯3 incompatible with partial diagram "D.h.w. / combi storage
tank"
45 = K¯9 incompatible with partial diagram "Solar"
51 = inadmissible reduction of B21 and B71
54 = d.h.w. heating BMU incompatible with partial diagram "Oil / gas"
55 = inadmissible reduction of B3 without d.h.w. heating BMU
203
Display of plant diagram identification number part 1
204
Display of plant diagram identification number part 2
205
Display of plant diagram identification number part 3
206
Display of plant diagram identification number part 4
Terminal test
210
Output test
(relay test)
---
Control mode according to the operating state
0
All outputs deactivated
1
Q101 ON
2
Q102 ON
3
Q103 ON
4
Q104 ON
5
Q105 ON
6
Q106 ON
7
Q107 ON
8
Q108 ON
9
Q109 ON
10
Q110 ON
211
Input test (sensor test)
1
Sensor at B101
2
Sensor at B102
3
Sensor at B103
4
Sensor at B104
5
Sensor at B105
6
Sensor at B106
7
Sensor at B107
8
Sensor at B108
9
Sensor at B109
10
Room sensor (PPS room unit)
11
Input H1 (ontact or DC 0...10 V)
12
Input E1 (AC 230 V)
212
Display of PPS communication
Query with the + / - buttons
- - -
No communication
1...12
PPS device address
0...255
Identification code
Setpoint / actual value of common flow
220
Display of the common flow temperature setpoint
---
No value available
221
Actual value of the common flow temperature
---
No value available
Flue gas temperature
222
Actual value of the flue gas temperature B8
---
No value available
223
Maximum value of the flue gas temperature display B8
---
No value available
To reset the maximum value to the actual value, press the + / - but-
tons simultaneously for 3 s
12/28
19.08.2002
74 319 0312 0 a
Range
Unit
1...99
0...99'999'999
0...99'999'999
0...99'999'999
0...99'999'999
0...10
1...12
--- / 1..12 /
0..255
0.0...140.0
°C
0...140
°C
–50...350
°C
–50...350
°C