8. Switch on power. The display must show something
(e.g. time of day). If not, the reason may be one of the
following:
-
No mains voltage
-
Main fuse blown
-
Mains isolator or main switch not set to ON
9. If one of the operating mode buttons flashes, a room
unit or contact H1 overrides the controller. Select op-
erating mode
on the room unit; switch off contact
H1.
General information about operation
Setting elements:
Setting knob
Display; an operating line is assigned to each setting
Buttons for selecting and adjusting setting values:
Next operating line below
Next operating line above
Decrease the displayed value
Increase the displayed value
Adopting a setting value:
The setting value is adopted by selecting the next op-
erating line (or by pressing one of the operating mode
buttons)
Entering --.- / --:-- / --- (deactivating a function):
depressed until
Keep
or
appears
Block jump function:
To select a single operating line quickly, 2 button
combinations can be used:
Operating elements
5
1 2 3 4 5 6 7 8 9 10
10
4
0
4
8
12
3
Info
7
8
9
2/28
19.08.2002
the required display
6
C
16
20
24
2
14
RVP540
74 319 0312 0 a
Press
and
to select the next line block above.
Press
and
to select the next line block below.
Setting procedure
1. Make settings on the operating lines according to the
instructions provided by your local Siemens HVAC
Products sales office.
2. Select plant type on operating line 100.
3. Make the required settings on the controller. All func-
tions and operating lines required for the selected type
of plant will be activated and can be set. Operating
lines that are not used will be hidden.
4. Enter the adjusted values in the table!
5. Set the general functions (independent of the type of
plant).
Commissioning and functional check
Specific operating lines for the functional check:
200 = output test
201 = input test
296 = functional test oil- / gas-fired boiler
345 = functional test solar
395 = functional test wood-fired boiler
545 = functional test d.h.w. storage tank
745 = functional test heating circuit
888 = output test P1
894 = output test Ux
If Er (ERROR) appears on the display: Refer to operating
line 50 to find the fault
20
26
1
8
°C
9
10
2392Z54a
An illuminated button or signal lamp indicates that the
relevant function is activated.
Front of RVP540 and RVP550
Siemens Building Technologies / HVAC Products
Room temperature setpoint knob
Adjustment of nominal room temperature setpoint
Setting buttons
Parameter settings (+ / -)
Operating line selection buttons (Prog)
Selection of parameters / switching operating lines
Display
Showing actual values and settings
Operating mode buttons heating circuit
Operating mode changes to:
Automatic operation
Continuous operation
Standby
Operating mode button d.h.w.
D.h.w. heating ON / OFF
Manual d.h.w. push
Function button with LED for manual operation
Manual operation ON / OFF
Green button with signal lamp
Green operation ON / OFF
Info button
Display of plant values
Connection facility for PC tool
Diagnostics and service with OCI69 / ACS69

Advertisement

loading

This manual is also suitable for:

Rvp540