GE Grid Solutions

2.4 I/O Peripheral Modules

The D20/D200 design is based on a distributed-processing architecture. As a result, the real-time
data acquisition and control software that interfaces with field points is installed on peripheral
modules, rather than on the main processor unit.
These I/O peripherals are intelligent modules that contain on-board microprocessors. They are
configured as slaves to the D20/D200 main processor. In this way, specific I/O processing is
distributed throughout the RTU to the appropriate I/O module.
D20 I/O peripherals communicate with the D20/D200 through a high speed, high-level data link
controller (D.20 Link) in the form of poll and response messages. The peripheral modules have a
serial communications port and a variable number of field connections.
The hardware construction of each module is similar (see Figure 18.) Each peripheral module
has common code stored in EPROM and a unique application configuration stored in RAM. The
base application code is stored on the D20/D200. At power up, the configuration and application
code are downloaded to the peripheral module from the D20/D200 main processor.
2.4.1 Types of I/O Peripherals
There are five basic types of I/O peripheral modules:
• D20S digital input
• D20A analog input
• D20K control output
• D20C combination input/output
• D20AC direct AC analog input
I/O peripheral modules are available with a variety of I/O point count support and termination
options. The following is a listing of the various D20 I/O peripherals that are currently available
from GE Grid Solutions:
Peripheral
D20A
32 analog inputs, standard version
D20AD
32 analog inputs, standard version
D20AX
32 analog inputs, standard version
D20AB
32 analog inputs, standard version
D20AZ
32 analog inputs, high-voltage version
D20S
64 digital inputs, standard version
D20SD
64 digital inputs, standard version
D20SX
64 digital inputs, standard version
D20SB
64 digital inputs, standard version
D20SZ
64 digital inputs, high-voltage version
GE Information
Table 6 D20/D200 I/O Peripherals
I/O Support
PRPI-019-3.00-10
D20/D200 Technical Overview
Termination
Compression
DB25
Disconnect
Barrier
Compression
Compression
DB25
Disconnect
Barrier
Compression
37