  • Page 1 ® BACnet Option Module Instruction Manual TR200 November 2009 BAS-SVX24B-EN Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 2: Table Of Contents

    Network Adjustable Frequency Drive Control Inputs and Out- puts Adjustable Frequency Drive Feedback to Network 5-15 Parameters Parameter Overview Parameter Description Troubleshooting Alarm, Warning and Extended Status Word Alarm Words Warning Words TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 3 LED Status TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 4: Copyright, Limitation Of Liability And Revision Rights

    Trane reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former or present users of such revisions or changes.
  • Page 5: Warnings, Cautions And Notices

    NOTE Indicates a situation that could result in equipment or property damage-only accidents. Note Indicates something important to be noted by the reader. ✮ Indicates default setting TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 6: High Voltage Warning

    (linking of DC intermediate circuit) and external 24 Vdc have been installed. Make sure that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair work. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 7 Installation at high altitude: 380–500 V, enclosure A, B and C: At altitudes above 6,561 ft [2 km], please contact Trane regarding PELV/Class II. 380–500 V, enclosure D, E and F: At altitudes above 9,842 ft [3 km], please contact Trane regarding PELV/Class II.
  • Page 8 15–125 hp 60–550 hp 600–1875 hp [11–90 kW] [45–400 kW] [450–1400 kW] Be aware that there may be high voltage on the DC link even when the LEDs are turned off. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 9: Safety Precautions

    Consequently, disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Failure to follow recommendations could result in death or serious injury. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 10: Protection Mode

    Note It is recommended to disable protection mode in hoisting applications (par.14-26 Trip Delay at Inverter Fault TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 11: Before Commencing Repair Work

    Grid configuration (grounded delta transformer leg, IT,TN, etc.) • Safety of low-voltage ports (PELV conditions). Consult the relevant clauses in these instructions and in the for information about the installation requirements. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 12: Introduction

    How to Install How to Configure the System Application Example For more detailed information including the full range of set-up options and diagnosis tools, refer to the chapters: How to Control the TR200 How to Access TR200 Parameters Parameters Troubleshooting...
  • Page 13 Network topology: Physical media: Shielded twisted pair Max. Distance at low speed: 3937 ft [1200 m] Transport mechanism Communication methods: Master/slave Baud Rates Supported: 9600, 19200, 38400, 76800 Termination: 120 ohm TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 14: Background Knowledge

    Introduction Assumptions This manual assumes you are using a Trane BACnet Option Card in conjunction with a Trane TR200 series adjustable frequency drive. It is also assumed that your master is a BMS or PC equipped with a serial commu-...
  • Page 15 Field Device Tool Sub index Input/Output International Standards Organization Liquid Crystal Display keypad Local Control Panel Light Emitting Diode Main Actual Value Motion Orientated Controller Main Reference Value Personal Computer TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 16: How To Install

    Serial communication bus option adaptor frame for the adjustable frequency drive. This frame is deeper than the standard frame, to allow space for the serial communication bus option beneath. Cable holders TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 17 Drop cable connection (i.e., T-connection) beyond the cable lengths indicated is not recommended, due to the increased risk of reflection occurring. Instead, Trane recommends direct connection of the adjustable frequency drive. Note that a repeater is a node in both of the two segments it connects. The number of adjustable frequency drives is based on a single master system.
  • Page 18 Cable type: twisted in pairs, 1 x 2, or 2 x 2, or 1 x 4 wires Shielding: Copper-braided shield or braided shield and foil shield Use of the same cable type throughout the entire segment is recommended to avoid impedance mismatch. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 19: Network Termination

    Terminal 63 is marked green. These two are the RS485 lines. Terminal 66 the signal ground for the RS485 transmitter. Maximum Cable Lengths Maximum total bus cable length: 4000 ft [1200 m] TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 20: Cable Routing

    The TR200 Series has various clamps and brackets to enable a proper ground connection of the BACnet cable shield.
  • Page 21: Ground Connection

    The ground connection must have low HF (high frequency) impedance. This can be achieved by connecting a large surface area of the cabinet to ground, for example by mounting the TR200 series on a conductive rear plate. Particularly when there are long distances between the stations in a BACnet network, it may be necessary to use additional potential equalizing cables, connecting the individual stations to the same ground potential.
  • Page 22: How To Configure The System

    9600 baud Minimum Response Delay 8-35 10 ms 10 ms Max Response Delay 8-36 5000 ms 5000 ms Table 4. 1: 1) Please see also section: Parameter Overview >Parameter List. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 23: Bibbs

    Bibb's ReadProperty Service ReadPropertyMultiple Service WriteProperty Service WritePropertyMultiple Service ConfirmedEventNotification Service UnconfirmedEventNotification Service GetEventInformation Service AcknowledgeAlarm Service ReinitializeDevice Service DeviceCommunicationControl Service I-Have Service Who-Has Service Who-Is Service I-am Service TimeSynchronization TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 24: Example Of A Simple Set-Up Of Bacnet

    How to Configure the System Example of a simple set-up of BACnet This example shows the necessary steps to set up the TR200 BACnet interface with the following system re- quirements: • MS/TP running at 38,400 baud • MAC address 20 for the TR200 •...
  • Page 25 How to Configure the System TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 26: How To Control The Adjustable Frequency Drive

    Motor Speed Low Limit [Hz] must be set to 0 Hz. Set the par.4-14 Motor Speed High Limit [Hz] to a value greater than the setting in par.3-03 Maximum Reference. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 27: Network Adjustable Frequency Drive Control Inputs And Outputs

    #29 Bus 5-95 Control Analog AO:3 6-63 Out X30/8 [mA] Analog AO:4 Output 26-43 X42/7[V] Analog AO:5 Output 26-53 X42/9[V] Analog AO:6 Output 26-63 X42/11[V] Table 5. 2: Analog outputs TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 28 Ext. 1 Integral AV:27 TR200 21-22 Time (Sec) Ext. 1 Differential AV:28 TR200 21-23 Time (Sec) Ext. 1 Dif. Gain AV:29 TR200 21-24 Limit AV:30 Reserved Table 5. 3: Analog values TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 29 How to Control the Adjustable Frequency Drive Change- Non-vola- Alarm TR200 Pa- Triggers Bus Object Read/ Object Name able De- tile RAM notifi- Write rameter Timeout scription Store cation AV:31 Ext. 2 Setpoint TR200 21-35 Ext. 2 Reference AV:32 TR200...
  • Page 30 1660/14* Digital Input P BI:15 Read 16-60/15 1660/15* Table 5. 5: Binary inputs Bl:7 - Bl:19 values are only available if the option is installed. *) Reserved for future options! TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 31 Option C Relay 7 BO:22 5-90/22 Output Option C Relay 8 BO:23 5-90/23 Output Reserved Output BO:24 5-90/24 P 590/24* Reserved Output 5-90/25 BO:25 P 590/25* Table 5. 6: Binary outputs TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 32 P 590/26* Reserved Output BO:37 5-90/27 P 590/27* Reserved Output BO:38 5-90/28 P 590/28* Reserved Output BO:39 5-90/29 P 590/29* Table 5. 7: Binay outputs cont. *) Reserved for future options! TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 33 ECB Overload BV:26 31-10/06 Trip BV:27 M2 Fault 31-10/07 BV:28 M3 Fault 31-10/08 ECB External In- BV:29 31-10/09 terlock ECB Manual BV:30 31-10/10 Override BV:31 Reserved Table 5. 8: Binary values TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 34 Service Trip P BV:75 16-91/03 1691/3 Service Trip P BV:76 16-91/04 1691/4 BV:77 No Flow 16-91/05 BV:78 Dry Pump 16-91/06 BV:79 Curve End 16-91/07 Table 5. 9: Binary values cont. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 35 DC Voltage Low 16-92/12 BV:117 DC Voltage high 16-92/13 BV:118 Line ph. loss 16-92/14 BV:119 No Motor 16-92/15 BV:120 Live Zero Error 16-92/16 Table 5. 10: Binary values cont. 5-10 TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 36 Reserved, P BV:151 16-93/15 1693/15 Reserved, P BV:152 16-93/16 1693/16 BV:153 KTY Temperature 16-93/17 BV:154 Drive Fan Failure 16-93/18 BV:155 ECB Failure 16-93/19 Table 5. 11: Binary values cont. TR200 BACnet 5-11 Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 37 Output Current BV:176 16-94/08 BV:177 Output Freq High 16-94/09 BV:178 Output Freq Low 16-94/10 BV:178 Brake Check OK 16-94/11 BV:180 Brake Max 16-94/12 Table 5. 12: Binary values cont. 5-12 TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 38 Triggers Bus Object Name able De- tile RAM Drive Par. Write cation Timeout scription Store SL LC Controller MSV:0 16-38 State Bit 13 & 14 MSV:1 Set-up selection in CTW TR200 BACnet 5-13 Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 39 The adjustable frequency drive has a built-in real-time clock. The standard real-time clock has no battery backup function (for real-time clock battery backup, selected TR200 option modules are available), which will lead to a time stop if the drive is unpowered. Some BACnet Masters can be programmed to send out the date and time as a broadcast message on a regular basis.
  • Page 40: Adjustable Frequency Drive Feedback To Network

    Control Site must be set to Digital and ctrl. word [0] or Controlword only [2]. Troubleshooting More detailed information and examples of logical relationship options are provided in the chapter. TR200 BACnet 5-15 Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 41 Max. AP- DU Length Segmenta- tion Sup- port Local Time Local Date APDU Timeout Number APDU Re- tries Max Mas- Max Info Frames Device Ad- dress Bind- Database Revision 5-16 TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 42 # of Notifica- tion Class Relinquish De- fault Polarity Active Text Inactive Text File type File size Modification Date Archive Read Only File Access Method *For commandable values only TR200 BACnet 5-17 Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 43 How to Control the Adjustable Frequency Drive 5-18 TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 44: Parameters

    8-75 Initialization Password “admin” String[19] Table 6. 1: BACnet specific parameter list TR200 Drive Instruction Manual, MG.12.HX.YY Please refer to the for a comprehensive parameter list or to the TR200 Drive Programming Guide, MG.12.JX.YY for detailed descriptions of parameters. TR200 BACnet...
  • Page 45: Parameter Description

    The function selected in par.8-04 Control Control Timeout Function Timeout Function will then be carried out. In LonWorks, the following variables will trigger the Control Word Time parameter: nviStartStop nviReset Fault TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 46 Reset Control Timeout toggles. Then the adjustable frequency drive resumes its original set-up. [1] * Resume set-up Resumes the set-up active prior to the timeout. TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 47: Control Profile

    Parameter group 8-7* is only visible when Adjustable Frequency Drive Option [9] is chosen. [0] * Communication according to the FC protocol as described in the TR200 Design Guide, RS 485 Installation and Set-up FC MC Same as...
  • Page 48 Parameters TR200 MetasysMG. device may have. Please see separate manual 12.NX.YY FC Option To be used when a gateway is connected to the integrated RS 485 port, e.g., the BACnet gateway. The following changes will take place: -The address for the adjustable frequency drive port will be set to 1 and par.8-31 Address, is now used to set the address for the gateway on the...
  • Page 49 Activates Start command via the serial communication bus/serial com- munication port OR via one of the digital inputs. Digital and control word NOTE: This parameter is active only when par.8-01 Control Site is set to [0] TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 50 Activate the set-up selection via the serial communication bus/serial communication port OR via one of the digital inputs. Digital and control word NOTE: This parameter is active only when par.8-01 Control Site is set to [0] TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 51 [0 - 0 N/A] Enter the password needed for execution of Drive Re-initialization from BACnet. Drive Option NOTE: This parameter is active only when par.8-30 Protocol is set to [9] TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 52: Troubleshooting

    3 in the Control Word, can the adjustable frequency drive resume operation. All alarms within the TR200 are represented by a single bit within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no alarm, while bit status TRUE [1] means alarm.
  • Page 53: Alarm Words

    Brake resistor short circuit 04000000 Reserved 08000000 Brake chopper fault 08000000 Reserved 10000000 Option change 10000000 Reserved 20000000 Drive initialized 20000000 Reserved 40000000 Safe Stop 40000000 Reserved 80000000 Not used 80000000 Reserved TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 54: Warning Words

    Low temperature 04000000 Reserved 08000000 Voltage limit 08000000 Reserved 10000000 Encoder loss 10000000 Reserved 20000000 Output frequency limit 20000000 Reserved 40000000 Not used 40000000 Reserved 80000000 Not used 80000000 Reserved TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 55: Led Status

    Unrecoverable fault drive is not re- sponding on internal bus Self test configuration takes place Gree ▂█▂█▂█▂█▂█ Running Module OK Gree ██████████ Recoverable fault • Configuration not OK, e.g, P830 • Drive tripped TR200 BACnet Download from Www.Somanuals.com. All Manuals Search And Download.
  • Page 56 November 2009 Supersedes BAS-SVX24A www.trane.com Trane has a policy of continous product and product data improvement and reserves the right to For more information, contact your local Trane office or e-mail us at comfort@trane.com change design and specifications without notice.
  • Page 57 Free Manuals Download Website h p://myh66.com h p://usermanuals.us h p://www.somanuals.com h p://www.4manuals.cc h p://www.manual-lib.com h p://www.404manual.com h p://www.luxmanual.com h p://aubethermostatmanual.com Golf course search by state h p://golfingnear.com Email search by domain h p://emailbydomain.com Auto manuals search h p://auto.somanuals.com TV manuals search h p://tv.somanuals.com...