BLUE SKY IPN ProRemote Installation And Operation Manual page 9

Ipn network compatible charge controller and battery system monitor/setup
Table of Contents

Advertisement

SET ACCEPT CHG
14.4V
SET FLOAT CHG
13.4V
SET EQUALIZ CHG
15.2V
SET EQUALIZ TIME
2.0HRS
SET AUTO EQUALIZ
30DAYS
SET T-COMP SLOPE
-5.00mV/C/C SEL►
SET FLOAT CURENT
1.5A/100AH SEL►
SET ACCEPT TIME
2.0HRS
Blue Sky Energy | USA |
www.blueskyenergyinc.com
BATTERY CHARGE PARAMETERS Menu
From Setup menu
SEL►
SEL►
SEL►
SEL►
SEL►
SEL►
Sets Absorption charge voltage setpoint.
Range 10.0 to 80.0V.
Sets Float charge voltage setpoint.
Range 10.0 to 80.0V.
Sets Equalize voltage setpoint.
Range 10.0 to 80.0V.
Sets Equalize time.
Range 0.5 to 10 hours.
Sets days between automatic Equalize. Range is 10 to 400 days. Fully
MANUAL equalization is selected by a setting of less than 10 days.
Sets charge voltage temperature compensation factor.
Range is -0.00 to -8.00mV/C/cell.
Sets Float Transition Current. Range 0.1 to 10.0A per 100 AH. A setting of
0 (zero) disables function such that full charge is based on Absorption
charge time only. See charge controller operators manual.
Sets Absorption charge time.
Range 0.0 to 10.0 hours.
FIGURE 5
Installation and Operation Manual
8