Blue Sky Energy – IPN ProRemote
➢ When Backlight is on, the IPN ProRemote can draw up to 100mA from the charge controller. For proper
operation of the shunt current measurement circuits, total voltage difference between the IPN ProRemote circuit
common and the shunt must be kept to less than 1.0V when Backlight is on and maximum charge or discharge
current is flowing in the system. If long network/power cables are used, wire size may need to be increased to keep
voltage difference between the "COM test point" and "SHUNT –" on the back of the IPN ProRemote to within
1.0V or less at all times. Table 3 below shows wire size for a more conservative recommended voltage drop limit
of 0.50V maximum.

MOUNTING

➢ CAUTION:. The unit is designed to mount into a standard US duplex wall mount box. It is not watertight and must
be protected from rain, snow and excessive moisture.
TROUBLESHOOTING GUIDE
SYMPTOM
Display blank
Display turns on, but
battery voltage shows – –
.–V rather than a number
13
MAXIMUM NETWORK/POWER CABLE LENGTH FOR 0.50V DROP
WIRE GAUGE
AWG
30 AWG
28 AWG
26 AWG
24 AWG
22 AWG
20 AWG
DETAILED DIMENSIONAL DRAWING
PROBABLE CAUSE
No power
IPN ProRemote not communicating
with charge controller
MAXIMUM RECOMMENDED CABLE LENGTH
FEET / METERS
45 / 13.7
73 / 22.2
117 / 35.7
187 / 57.0
295 / 89.9
475 / 144.8
TABLE 3
FIGURE 8
ITEMS TO EXAMINE OR CORRECT
Charge controller not properly powered.
Network cable faulty, not plugged in or cable pins do not swap per Figure
7.
Network cable faulty.
Charge controller or IPN ProRemote may have locked up, re-boot by
momentarily removing battery and PV power from charge controller.
One charge controller is not set to Master, or more than one charge
controller is set to Master.
Controller-to-controller network cable not wired A-to-A, B-to-B, or wires
are open or short.