Chapter 7

SSC Alarm Cabling

This chapter describes how to cable the alarm contacts on the System Status Card (SSC).
It includes the following sections:
CO Alarm Interface
Alarm Cutoff (ACO)
Alarm Connector Pinout
Electrical Characteristics
CO Alarm Wiring Example
Caution:
cabling only. This interface MUST NOT be metallically connected to interfaces that connect to the outside plant (OSP)
or its wiring. This interface is designed for use as an intra-building interface only (Type 2 or Type 4 ports as described
in GR-1089-CORE, Issue 5) and requires isolation from the exposed OSP cabling. The addition of Primary Protectors is
not sufficient protection in order to connect these interfaces metallically to OSP wiring.
The CO alarm interface of the SSC is suitable for connection to intra-building or unexposed wiring or