▀ Environmental Specifications

Clearance

Ensure that the equipment rack or cabinet hardware does not hinder air flow at any of the intake or exhaust vents. Allow
approximately 0.9 meter (36 inches) at the front and rear of the chassis for air flow and maintenance access.
Caution:
figure below). These units are very large and require additional clearance from cable management bars, PDUs, etc.
Figure 8.
▄ ASR 5500 Installation Guide
30
The rear clearance is also necessary for removing and replacing the rear cards and fan trays (see the
Rear Clearance Zone
Technical Specifications