Function Test, Measurement Of The Load Current With Schuko Measurement Adapter (Option) - Unitest Telaris 0751 Instruction Manual

Table of Contents

Advertisement

Function Test, Measurement of the Load Current
6.7 Function Test, Measurement of the
Load Current with
Schuko Measurement Adapter (Option)
6.7.1
General Information regarding the
Function Test
To complete a test procedure, the appliance
UNITEST TELARIS 0751 offers the function test fa-
cility. This test checks the UUT function and meas-
ures the load current consumption.
An external Schuko Measurement Adapter to meas-
ure the PE current, the differential current, and the
load current must be connected to the TELARIS
0751 (Cat. No. 9095).
In compliance with DIN VDE 0701, the function
test must be performed after completion of the
safety test after repair or modification of an
electrical apliance. For repeat tests in compli-
ance with DIN VDE 0702 no function test is re-
quired.
The function test may only be performed after
successful safety test.
The UUT is put into operation for this test, i.e.
it will be supplied with mains voltage. For this,
the UUT must be switched on. Motor driven
UUTs or UUTs equipped with heating units may
cause a danger for the controller (observe the
UUT instruction manual!).
Observe that mains voltage is already present
when plugging in the mains plug of the Schuko
Measurement Adapter! UUTs that are already
switched on are put into operation immediate-
ly after the plug-in!
40
The Schuko Measurement Adapter is not
equipped with built-in fuses. Observe that
overcurrent and short-circuit protection must
be ensured by the supplying mains system.
Therefore, the Schuko Measurement Adapter
may only be connected to a functional and cor-
rectly wired and grounded mains socket, pro-
tected at maximum 16 A!
The maximum output current of the mains
socket of the Schuko Measurement Adapter
amounts to 16A! The Schuko Measurement
Adapter may not be used for continuous meas-
urements.

Hide quick links: