GE C30 Instruction Manual page 313

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 8 of 39)
ADDR
REGISTER NAME
40C0
DNP IIN time synchronization bit period
40C1
DNP message fragment size
40C2
DNP client address 3
40C4
DNP client address 4
40C6
DNP client address 5
40C8
DNP number of paired binary output control points
40C9
DNP TCP connection timeout
40CA
Reserved (22 items)
40E0
TCP port number for the IEC 60870-5-104 protocol
40E1
IEC 60870-5-104 protocol function
40E2
IEC 60870-5-104 protocol common address of ASDU
40E3
IEC 60870-5-104 protocol cyclic data transmit period
40E4
IEC 60870-5-104 current default threshold
40E6
IEC 60870-5-104 voltage default threshold
40E8
IEC 60870-5-104 power default threshold
40EA
IEC 60870-5-104 energy default threshold
40EC
IEC 60870-5-104 power default threshold
40EE
IEC 60870-5-104 other default threshold
40F0
IEC 60870-5-104 client address (5 items)
4104
IEC 60870-5-104 redundancy port
4005
Reserved (59 items)
4140
DNP object 1 default variation
4141
DNP object 2 default variation
4142
DNP object 20 default variation
4143
DNP object 21 default variation
4144
DNP object 22 default variation
4145
DNP object 23 default variation
4146
DNP object 30 default variation
4147
DNP object 32 default variation
Ethernet switch (Read/Write Setting)
4148
Ethernet switch IP address
414A
Ethernet switch Modbus IP port number
414B
Ethernet switch Port 1 Events
414C
Ethernet switch Port 2 Events
414D
Ethernet switch Port 3 Events
414E
Ethernet switch Port 4 Events
414F
Ethernet switch Port 5 Events
4150
Ethernet switch Port 6 Events
Ethernet switch (Read Only Actual Values)
4151
Ethernet switch MAC address
4154
Ethernet switch Port 1 Status
4155
Ethernet switch Port 2 Status
4156
Ethernet switch Port 3 Status
4157
Ethernet switch Port 4 Status
4158
Ethernet switch Port 5 Status
4159
Ethernet switch Port 6 Status
415A
Switch Firmware Version
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) function
4169
Simple Network Time Protocol (SNTP) server IP address
416B
Simple Network Time Protocol (SNTP) UDP port number
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
GE Multilin
RANGE
UNITS
1 to 10080
30 to 2048
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 32
10 to 65535
0 to 1
1 to 65535
0 to 1
0 to 65535
1 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 4294967295
0 to 1
0 to 1
1 to 2
1 to 3
0 to 3
0 to 3
0 to 3
0 to 3
1 to 5
0 to 5
0 to 4294967295
1 to 65535
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
---
0 to 2
0 to 2
0 to 2
0 to 2
0 to 2
0 to 2
0.00 to 99.99
0 to 1
0 to 4294967295
1 to 65535
0 to 1
C30 Controller System
B.4 MEMORY MAPPING
STEP
FORMAT
min
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F126
---
1
F001
---
1
F001
---
1
F001
---
1
F523
---
1
F524
---
1
F523
---
1
F523
---
1
F001
---
1
F525
---
1
F003
---
1
F001
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F072
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
0.01
F001
---
1
F102
---
1
F003
---
1
F001
---
1
F126
DEFAULT
1440
240
0
0
0
B
0
120
0
2404
0 (Disabled)
0
60
30000
30000
30000
30000
30000
30000
0
0 (No)
0
2
2
0 (1)
0 (1)
0 (1)
0 (1)
1
0 (1)
3232235778
502
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0
0 (Disabled)
0
123
0 (No)
B-15

Advertisement

Table of Contents
loading

Table of Contents