Iec 61850 Goose Analogs - GE C30 Instruction Manual

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE ANALOG
 INPUT 1
MESSAGE
MESSAGE
MESSAGE
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE analog input is defined by the
GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other C30 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
Table 5–12: GOOSE ANALOG INPUT BASE UNITS
ELEMENT
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
The GOOSE analog input FlexAnalog™ values are available for use in other C30 functions that use FlexAnalog™ values.
GE Multilin


IEC 61850 GOOSE ANALOGS

ANALOG
1 DEFAULT:
1000.000
ANALOG
1 DEFAULT
MODE: Default Value
GOOSE ANALOG
1
UNITS:
GOOSE ANALOG
1 PU:
1.000
is set to "Default Value".This setting is stored as an IEEE 754 / IEC 60559 floating
BASE UNITS
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
C30 Controller System
5.7 INPUTS AND OUTPUTS
5.7.12 IEC 61850 GOOSE ANALOGS

GOOSE ANALOG INPUT 1(32)
Range: –1000000.000 to 1000000.000 in steps of 0.001
Range: Default Value, Last Known
Range: up to 4 alphanumeric characters
Range: 0.000 to 1000000000.000 in steps of 0.001
ANALOG 1 DEFAULT
setting for the two transducers configured
 I
for the +IN and –IN inputs
BASE
setting.
5
5-121