0. IMPORTANT SAFETY INSTRUCTIONS This manual contains important instructions for the unit that should be followed during installation and maintenance of the UPS and batteries. Before attempting to wire or operate the unit, read all instructions thoroughly. Install the on-line UPS in a well ventilated area, away from flammable liquids and gases. Do not let the unit come in contact with water.
Page 7
Parallel redundancy: No need of extra parallel control card, you can expand the total backup capacity by simply linking another unit via a DELTA cable. A single cabinet can install four power modules and each module has 20KVA capacity. As a result, NH-series can backup up to 80KVA in one cabinet.
1-1. Advanced Features Power Rating: 15/20/30/40/60/80 KVA ( 15/20/30/40KVA can be with internal battery ). Up to 4 modules work in parallel in one single cabinet 1+1 parallel redundant expansion and no need of extra parallel control card. Maximum total output power is 160KVA.
2. Operation Delta NH-series operates in four basic modes: 2-1 Normal Mode (Single Installation) RESERVE LOAD MAIN Fig. 2-1 Normal Mode Block Diagram Under normal mode, util ity power supplies to the rectifier and the n transferred into DC power to supply the inverter and charge the batteries.
When there is a power event (blackout, transient, surge, fluctuation…), UPS will automatically switch from normal mode into backup mode. Battery (internal or external) wil provide emergency pow er to the inverter and then the loads. (Ref er to Fig. 2-2) Reserve Mode (Single Installation) RESERVE LOAD...
2-4 Bypass Mode (Single Installation) RESERVE LOAD MAIN Fig. 2-4 Bypass Mode Block Diagram Under maintenance or repair service condition, you will need to cut off the UPS power but not the power to your equipment. Make sure the reserve power exists first, then manually switch UPS into bypass mode.
2-5 Normal Mode (Parallel) elta NH-series provide 1+1 parallel combination to get redundancy or expand the total capacity. RESERVE MAIN UPS1 LOAD RESERVE MAIN UPS2 Fig. 2-5 Normal Mode in parallel redundancy Under this inst allation,the loading is shared by two UPS units. If there is something wrong in one of them, the loading will be totally handle by another.
2-6 Backup Mode (Parallel) RESERVE MAIN UPS1 LOAD RESERVE MAIN UPS2 Fig. 2-6 Backup Mode in parallel redundancy Loading is shared by two UPS units when there is blackout. (Refer to Fig. 2-6)
2-7 Reserve Mode (Parallel) RESERVE MAIN UPS1 LOAD RESERVE MAIN UPS2 Fig. 2-7 Reserve Mode in parallel redundancy The same as chapter 2-3 except two UPS share the loading. (Refer to Fig. 2-7)
2-8 Bypass Mode (Parallel) RESERVE MAIN UPS1 LOAD RESERVE MAIN UPS2 Fig. 2-8 Bypass Mode in parallel redundancy The same as chapter 2-4 except two UPS share the load. Remember that both UPS should be switched into bypass mode. (Refer to Fig. 2-8)
2-9 Hot Standby Redundancy If you just want to double insurance the UPS operation, you can utilize one extra UPS to be the reserve source of main UPS. This installation will make sure the output power source for loading is still present even when the main UPS malfunctions. (Refer to Fig.
-2-1 Front Panel LCD Display and Control Panel LED indicators Power Modules I/P and O/P Protectors 1. LCD Displa y and Control Panel / LED indicators : Display UPS st atus and message Setup parameters and control buttons On/Off UP EPO: Emergency Power Off Please refer to Chapter 6-1 for more det ails.
(2) Parallel link communication (3) Input and Output Dry Contact (4) RS232 : Delta’s software ”UPSentry Smart 2000” or “InsightPower Manager” are optional choice for central monitoring and control purpose) 2. Power Module and wiring: - Remove the cover, you can perform wiring for power modules.
3-3 p S ecification Table 3-1 Delta NH-series Technical Data Capacity 15kVA/12KW 20kVA/16KW 30kVA/24KW 40kVA/32KW 50kVA/40KW 60kVA/48KW 80kVA/64KW 220/380 , 230/400 , 240/415 ting Voltage ( 3Φ 4W+Earth ) % Volt age regulation -25 ~ +20 ut current harmonic %...
4. Installation 4-1 Before Installation Due to different installation environment, we strongly recommend you to read this manual carefully before installation. Only qualified service personnel can perform installation and maintenance. 4-2 Package Inspections External It’s not predictable that UPS or battery pack will suffer what kind of impact or accident during transportation.
Charging procedure: Connect UPS to the utility. If external battery pack is ordered, please connect the battery pack to the UPS. Start UPS. At this time, UPS will charge the battery by internal charging circuit. 3. Remain sealed as original packing. Prevent any possible damage from mouse or similar creatures.
4-5 Location 4-5-1 Moving 1. NH-series UPS has casters to roll at a short distance to your desired location. Under unpacking procedure, employ a suitable machine with sufficient capacity to move UPS. Please pay extremely attention when unbolt UPS from shipping pallet. Prevent any accident caused by unexpected moving.
Table 4-2 Floor Loading for External Battery Pack 40 pcs Capacity (Ah) 12V/26AH Weight (kg) Floor Loading 1064 (kg/㎡) 4-5-3 Environment 1. NH-series is for in-house use only. 2. The installation space should be conditioned at temperature 25 C, related humidity <90%. 3.
4-6 Wiring 4-6-1 Preparations: 1. De-energize all input (AC or DC) or output power source of UPS before installing cables or making any electrical connections. 2. Make sure that all cables are correctly marked according to the purpose. Also the polarity, phase and diameter.
Page 27
Wiring procedure: 1. Remove cover at the rear side. See Fig. 4-1 Remover Cover Input Bypass Input External Battery Output Fig. 4-1 Wiring Terminal Grounding Terminal Terminal block (Refer to Fig 4-1): Input / Bypass : Ph-R、S、T and Neutral Output : Ph-R、S、T and Neutral External Battery : Positive(+), Negative(-) and neutral Grounding : Protection 2.
Page 28
6. Confirm UPS output circuit breaker (Q4) is cut off. 7. According to UPS model you select, using suitable cable and lug (Refer to Table 4-3). 8. Connect all cables to the right terminal or location as indicated (Refer to Fig. 4-1). Q1: Input Circuit Breaker Q2: Bypass Input Circuit Breaker Q3: Manual Bypass Circuit Breaker...
Page 29
Table 4-3 Input/Output Electrical Data Input Output Input Cable Reserve Reserve Output Output Battery Battery Breaker (mm²) Breaker Cable Breaker Cable Cable Fuse (mm²) (mm²) (mm²) 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 220/380 * Please follow the statute according to the installation region, select suitable breaker and cable.
-7 Interface Smart Card Slot RS232 PARALLEL OUTPUT DRY CONTACT Parallel RS232 Com. Port Communication Port Input Dry Contact Dry Contact Output Fig. 4-5 Interface -7-1 Input Dry Contact P1:REPO (Remote Emergen cy Power Off) 2:Input contact (Two sets) P3:External Battery Cabinet Temperature 1 P4:External Battery Cabinet Temperature 2 P5:External Battery Cabinet Temperature 3...
Page 33
4. P7 : External Battery Status (Optional) You can order this optional cable to detect the status of external battery cabinet. This function is only for cabinet ordered from DELTA. Pin1:+12V Pin2:Detection cable connected Pin3:Extern al battery cabinet breaker’s status :...
Page 35
NH series provide 6 dry contact outputs. These contacts can be setup to normal open or normal close. The default message is: Contact Message Description Pin1-2 Load on inverter UPS is working normally Pin3-4 Load on auto bypass UPS is in bypass mode Pin5-6 Mains1 input fail when Utility is blackout or abnormal.
Use the parallel communication cable within the accessory pack. Link UPS with unsuitable cable may result in accident. 4-7-5 Smart Card Slot NH series provide two smart slots and DELTA develops many powerful smart cards for different applications. 1. SNMP Card (Optional)
Page 37
Features: SNMP agent and web server implemented for UPSSupport the following protocols: ARP, IP, ICMP, SNMPv1, SNMPv3 USM, UDP, TCP, HTTP, FTP, TFTP, SMTP, BOOTP, SNTP, DN and Telnet Security login by MD5 Users level management Firmware upgrade for new features through TFTP Batch configuration through FTP Save UPS event log and history values in EEPROM Schedule shutdown, restart and test UPS...
2. Programmable Relay I/O Card (Optional) Features: UPS status information presented as 6 contact closuresProgrammable output contacts, monitors the UPS events that users really concern in different application practices Configurable UPS shutdown delay time Configurable input signal as shutdown UPS or battery test Has the ability to protect up to 6 computers unattended shutdown gracefully Technical Spec.
Page 39
I/O Definition GND-R: Relay Grounding Common: 12 ~ 24VDC Default Summary Alarm Input Power Fail Battery Low UPS in Bypass Mode Overload Over Temperature Input : Remote shutdown or battery test Tx: Transmit to PC, connect to RS232 pin-2 Rx: Receive from PC, connect to RS232 pin-3 GND-C: Ground for configuration, connect to RS232 pin-5 OFF(Default) Normal Open...
I/O Definition Ground for RS232 RS232-Tx Tx to PC RS232-Rx Rx from PC RS422-T+ T+ for RS422 or RS422-D+ D+ for RS485 RS422-T- T- for RS422 or RS422-D- D- for RS485 RS422-R+ R+ for RS422 RS422-R- R- for RS422 4-8 Other Optional Accessories 1.
Page 41
2. SNMP+ 5 Ports Switching Hub Features: Fast ethernet 5 ports 10/100M smart switching hub SNMP agent and web server implemented for UPS Support the following protocols: ARP, IP, ICMP, SNMPv1, SNMPv3 USM, UDP, TCP, HTTP, FTP, TFTP, SMTP, BOOTP, SNTP, DN and Telnet Security login by MD5 Users level management Firmware upgrade for new features...
5. Operating Procedure 5-1 Start up Procedure (Single Unit) Preliminary Check: All circuit breakers are cut off, including the breaker or fuse of the external battery cabinet. Confirm there is no voltage potential between NEUTRAL and Ground. Confirm the input power source matches the rating (Voltage、frequency、phase and battery ) of UPS you install.
5-3 Powering Down (Single Unit) This procedure will shutdown UPS and also the output for loads. Confirm all loads are turned off first! Press button ” O ” for 3 seconds until you hear a beep then release button. If originally UPS is in - normal mode : Then UPS will transfer to bypass mode.
Start up procedure: 1. Connect two UPS with parallel communication cable. Ensure the connector is fastened to the DB9 port. 2. If there is an external battery cabinet is connected, switch on the breaker of external battery cabinet. 3. Switch on “Q2” of each UPS. The LCD display will show ”ON AUTO BYPASS”. 4.
Page 45
5-7 Manual Bypass Start ups (Parallel Redundancy) Only for maintenance purpose, you can turn on manual bypass switch. If you switch on Q3 under normal condition, then inverter will turn off and output will be supplied by manual bypass source. 5-7-1 Online Mode transfers into Manual Bypass Mode 1.
6. Display and Configuration 6-1. Control Panel Fig. 6-1 Control Panel 1. Normal (Green): Turn on when UPS input power is normal Battery (Amber): Turn on when UPS is in backup mode Bypass (Amber): Turn on when UPS is in manual bypass mode Fault (Red): Turn on when any fault occurs LCD Display: LCD screen, Multi-language (Chinese tradition/Big5, English) 6.
6-3 Default Screen After UPS starts up and completes the self-test, screen will show: LOAD UNPROTECTED LOAD UNPROTECTED ON AUTO BYPASS ON AUTO BYPASS BYPA. BYPA. MAINS MAINS 1. When any event occurs, you will see the sign “!” flashes. You can press “ ” to see the details.
6-3-1 Status Display LCD display will show the different status of UPS: LOAD NOT POWERED BYPA. MAINS This message means: The loads behind UPS are not powered. UPS cuts off the output. Maybe due to: - UPS automatically shutdown by itself. - Manually switch off the output circuit breaker.
Page 50
SOFT START… BYPA. MAINS This message means UPS startup by battery power. LOAD UNPROTECTED LOAD UNPROTECTED ON AUTO BYPASS ON AUTO BYPASS BYPA. BYPA. MAINS MAINS This message means: UPS is in bypass mode. In the mean time, main power source and battery are cut off.
Page 51
LOAD PROTECTED ONLINE MODE BYPA. MAINS This message means: UPS is operating under normal condition (normal mode). LOAD PROTECTED ON BATTERY / BAT REM: 1123 MIN BYPA. MAINS This message means: UPS is in battery backup mode. Loads are supplied by battery power.
Page 52
LOAD PROTECTED ON BATTERY / BAT REM: 2 MIN BYPA. MAINS This message means: UPS is in battery backup mode and remaining backup time only 2 minutes left. Battery power is nearly exhausted. LOAD PROTECTED BAT TEST BYPA. MAINS This message means: UPS is performing “battery test”.
Page 53
LOAD PROTECTED ECO MODE BYPA. MAINS This message means: UPS is in ECO (Economic Operation) mode. Loads are supplied power by bypass source. LOAD UNPROTECTED ON MANUAL BYPASS BYPA. MAINS This message means: UPS is in manual bypass mode. When service personnel performs the maintenance work, UPS must be transferred into this mode first.
6-4 Main Menu Press “ ” in default screen will change into the main menu: ress “ ” or ” ” to select desired item, then confirm by press “ ”. MEASURE Move cursor by “ ” or ” ” to “Measure”. Select this item by press ” ”...
6-5 UPS SETUP Move c ursor by “ ” or ” ” to “Measure”. Select this item by press ” ” Before get into the “UPS SETUP”, you have to login first: 1. The login screen is as right. Move cursor to select your correct ID, then press ”...
a. BYPASS SETUP Move cursor by “ ” or ” ” to “BYPASS SETUP”. Select this item by press ” ” 1. Move cursor by “ ” or ” ” to select “VOLTAGE RANGE” or “FREQUENCY RANGE”. Press ” ” to confirm the choice. 2.
b. OUTPUT SETUP Move cursor by “ ” or ” ” to “OUTPUT SETUP”. Select this item by press ” ” All the parameter in this segment can only be changed under “Bypass Mode”. 1. Move cursor by “ ” or ” ” to select the desired item.
c. BATTERY SETUP Move cursor by “ ” or ” ” to “BATTERY SETUP”. Select this item by press ” ” All the parameters in this segment can only be changed under “Bypass Mode”. 1. Move cursor by “ ” or ” ” to select the desired item.
d. LOCAL SETUP Move cursor by “ ” or ” ” to “LOCAL SETUP”. Select this item by press ” ” 1. Move cursor by “ ” or ” ” to select the desired item. Press ” ” to confirm the choice. 2.
Page 61
5. Move cursor by “ ” or ” ” to setup the audible alarm. Press ” ” to confirm the choice. 6. Move cursor by “ ” or ” ” to s etup the contrast of LCD screen. Press ” ”...
6-6 Maintenance e cursor “ ” or ” ” to the ”MAINTENANCE” in the main menu, confir by press “ ”. 1. Move cursor by “ ” or ” ” to select the desired item. & & Press ” ” to confirm the choice. 2.
Page 64
Press “ ” to execute “MANUAL ATTERY TEST”. (This item is only accessible for dministra r. Password will be nfirmed gain!) Press “ ” to execu te “BUZZER AND ED TEST”. (This item is only accessible for administrator! Password will be confirmed again!) Press “...
7-2 UPSentry Smart 2000 DELTA develops a power software family to easily integrate UPS into your system. “UPSentry Smart 2000” supports all popular OS such as Windows, Linux, FreeBSD …etc. Advanced Features: Supports RS232 and USB protocols Multi-lingual design (English, French, German, Spanish, Portuguese, Italian, Polish,...
7-2-1 Flexible Management Tools “UPSentry Smart 2000” provides powerful tools for administrator of data center, MIS, IDC. 1. Real-Time Monitoring, record and analysis Real-Time meters: 4 ( single phase ) or 12 ( 3 phases ) meters. Each meter is user-defined to display power information (voltage, current, frequency…) or UPS’s status.
Page 68
Shutdown OS Event Log Transmit an Execute External Popup audible message Command Message . Overload Warning Setup Administrator can setup tw o stage of overload limit between 0%-100%. Warning message will popup when reach the loading limit. 4. Scheduled Shutdown/Auto Restart UPSentry Smart 2000 can perform OS shutdown process before UPS turns off.
7-3 InsightPower Manager For data center or large scale factory, administrator need a convenient tool to centrally control and monitor UPSs. DELTA develops “InsightPower Manager” to achieve this purpose. Features: Centralized UPS management system via TCP/IP network Supports RS232, RS485 and...
Page 70
Event Log: Record events and operation by date/time Generate historical report and can be transferred into EXCEL file Setup a periodically analyzing report. Network InsightPower InsightPower Manager Service Manager Monitor SNMP SNMP RS232/485 SNMP RS232/485 InsightPower Manager Monitor Remote UPS Monitoring...