PSR – The compact range

Overview

Softstarter. Type
Normal start
PSR3
In-line connected
(400 V) kW 1.5
IEC, Max. A 3.9
(440-480 V) hp 2
UL, Max FLA 3.4
400 V, 40 ºC
Manual motor starter (50 kA) type
Using manual motor star-
ters type 1 coordination will
be achieved
Fuse protection (50 kA) gG Fuse
Using gG fuses type 1 co-
ordination will be achieved
10 A
Switch fuse, type
Suitable switch fuse for the
above gG fuses
Thermal overload relay
Overload protection is used
to protect the motor from
over heating
Line contactor, type
The line contactor is not
required for the softstarter
itself but often used to open
if OL trips
By-pass contacts
Using by-pass will reduce
the power loss and allow
more starts per hour
PSR3 ... PSR16
PSR6
PSR9
PSR12
PSR16
3
4
5.5
7.5
6.8
9
12
16
3
5
7.5
10
6.1
9
11
15.2
MS116
16 A
25 A
32 A
OS32GD
TF42DU
AF9
AF12
AF16
PSR25 ... PSR30 PSR37... PSR45
PSR25
PSR30
PSR37
11
15
18.5
25
30
37
15
20
25
24.2
28
34
MS132
MS450
50 A
63 A
100 A
AF26
AF30
AF38
Built-in
PSR60 ... PSR105
PSR45
PSR60
PSR72
PSR85
22
30
37
45
45
60
72
85
30
40
50
60
46.2
59.4
68
80
MS495
125 A
200 A
OS125GD
OS250GD
TA75DU
A50
A63
A75
1SFC132005C0201, rev.F | Softstarters 9
PSR105
55
105
75
104
250 A
TA110DU
A95
A110