ABB PSR Manual page 15

Softstarters
Table of Contents

Advertisement

PSS – The flexible range
Description
The PSS Softstarter can be selected
according to the rated motor power
in normal duty applications like
pumps,
compressors,
elevators,
escalators, short conveyor belts and
bow thrusters. See page 18-19.
For heavy duty applications like
centrifugal fans, crushers, mixers,
mills, stirrers and long conveyor belts,
select a softstarter from page 20-21.
In-Line
Inside Delta
100 A
58 A
100 A
100 A
In-Line and Inside Delta connection
of PSS18/30 ... PSS300/515
Settings
1
2
4
3
1SFT 98899-031
U ini
3
1
Start
Ramp time START = 1 ... 30 sec
1
Ramp time STOP = 0 ... 30 sec
2
U end
3
Initial voltage U
Level of current limit = 1.5 ... 4xI
3
When current limit is used, initial voltage and
end voltage is fixed at 40 %
4
Switch for In-line or Inside Delta connection
2
Stop
Screw mounting
Built-in signal relays
for fault and by-pass
Possibility to connect external
current transformer for current
limit function
Transparent lid to
protect the settings
LED indications:
Power supply on
Completed start ramp
General fault
(motor side or unit)
External fault
Clear markings on the front
and end voltage = 40 ... 70 %
ini
.
e
1SFC132005C0201, rev.F | Softstarters 15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

PssPstbPse

Table of Contents