ABB PSR Manual page 46

Softstarters
Table of Contents

Advertisement

PST(B) – The advanced range
Technical data
Major possible settings and the displayed text and the set default values
Description
Setting current for overload, locked rotor etc.
Time for start ramp
Time for stop ramp
Initial voltage for start ramp
End voltage for stop ramp
Step down voltage
Level of the current limit.
Selection of Kick start
Level of Kick start if selected
Time for Kick start if selected
Selectable range for start ramp
Selectable range for stop ramp
Overload protection
Overload Class
Overload Class, Dual type, Start Class
Overload Class, Dual type, Run Class
Type of operation for overload protection
Locked rotor protection
Trip level for locked rotor protection
Trip time for locked rotor protection
Type of operation for locked rotor protection
Underload protection
Trip level for Underload protection
Trip time for Underload protection
Type of operation for Underload protection
Phase imbalance protection
Trip level for phase imbalance protection
Type of operation for phase imbalance protection
High current protection
Type of operation for high current protection
Phase reversal protection
Type of operation for phase reversal protection
PTC protection
Type of operation for PTC protection
An external Bypass contactor is used
High current warning
Trip level for high current warning
Low current warning
Trip level for low current warning
Overload warning
Trip level for overload warning
Thyristor overload warning
Type of operation for phase loss fault
Type of operation for by-pass doesn't close
Type of operation for by-pass doesn't open
Type of operation for fieldbus fault
Type of operation for frequency fault
Type of operation for heat sink over temperature fault
Type of operation for thyristor short circuit fault
Function of programmable input In_0
Function of programmable input In_1
Function of programmable relay output K4
Function of programmable relay output K5
Function of programmable relay output K6
Control of the softstarter with fieldbus
Number of sequences for sequence start.
Language to use on display
Password for display
Start mode
Stop mode
Torque limit
Analog output
Analog output, reference
Analog output, type of value
46 Softstarters | 1SFC132005C0201, rev.F
Text on display (Eng) Values on display
Setting I
9.0 ...1207 A divided into 19 overlapping ranges.
e
Start Ramp
1 ... 30 s, 1 ... 120 s (Range depends on Start Range)
Stop Ramp
0 ... 30 s, 0 ... 120 s (Range depends on Stop Range)
Init Volt
30 ... 70 %
End Volt
30 ... 70 %
Step Down
30 ...100 %
Current Lim
1.5 ... 7.0 x I
Kick Start
Yes, No
Kick Level
50 ... 100 %
Kick Time
0.1 ... 1.5 s
Start Range
1 ... 30 s, 1...120 s
Stop Range
0 ... 30 s, 0 ... 120 s
Overload
No, Normal, Dual
OL Class
10 A, 10, 20, 30
OL Class S
10A, 10, 20, 30
OL Class R
10A, 10, 20, 30
OL Op
Stop-M, Stop-A, Ind
Locked Rotor
Yes, No
Lock R Lev
0.5 ... 8.0 x I
Lock R Time
0.2 ... 10 s
Lock R Op
Stop-M, Stop-A, Ind
Underload
Yes, No
Underl Lev
0.4 ... 0.8 x I
Underl Time
1 ... 30 s
Underl Op
Stop-M, Stop-A, Ind
Phase Imb
Yes, No
Ph Imb Lev
10 ... 80 %
Ph Imb Op
Stop-M, Stop-A, Ind
High I
Yes, No
High I Op
Stop-M, Stop-A, Ind
Phase Rev
Yes, No
Ph Rev Op
Stop-M, Stop-A, Ind
PTC
Yes, No
PTC Op
Stop-M, Stop-A
Ext ByPass
Yes, No
Warn I=High
Yes, No
Wa I=H Lev
0.5 ... 5.0 x I
Warn I=Low
Yes, No
Wa I=L Lev
0.4 ...1.0 x I
Warn OL
Yes, No
Wa OL Lev
40 ... 99 %
Warn SCR OL
Yes, No
Ph Loss Op
Stop-M, Stop-A
BP open Op
Stop-M, Stop-A
BP closed Op
Stop-M, Stop-A
FB Fault Op
Stop-M, Stop-A
Freq F Op
Stop-M, Stop-A
HS Temp Op
Stop-M, Stop-A
SCR SC Op
Stop-M, Stop-A
In0
None, Reset, Enable, Jog, DOL, Start 2, FB-Dis
In1
None, Reset, Enable, Jog, DOL, Start 3, FB-Dis
Relay K4
Run, TOR, Event
Relay K5
Run, TOR, Event
Relay K6
Run, TOR, Event
Fieldb Ctrl
Yes, No
No of Seq
No, 2, 3
Language
US/UK, FI, SE, PT, NL, IT, FR, ES, DE, CN, RU, TR, PL, CZ
Password
No, 1 ... 255
Start Mode
Volt, Torque
Stop Mode
Volt, Torque
Torque limit
20 ... 200 %
Analogue Out
Yes, No
Anl Ref
0 ...10 V, 0 ... 20 mA, 4 ... 20 mA
Anl Type
I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot, TmpSCR, cosPhi
e
e
e
e
e
Default value
See table, page 48
10 s
0 s
30 %
30 %
100 %
4.0 x I
e
No
50 %
0.2
1 ... 30 s
0 ... 30 s
Normal
10
10
10
Stop-M
No
4.0 x I
e
1.0 s
Stop-M
No
0.5 x I
e
10 s
Stop-M
No
80 %
Stop-M
No
Stop-M
No
Stop-M
No
Stop-M
No
No
1.2 x I
e
No
0.8 x I
e
No
90 %
No
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Reset
Reset
Run
TOR
Event
No
No
US/UK
Volt
Volt
150 %
No
4 ...20 mA
I Amp