Overview - ABB PSR Manual

Softstarters
Table of Contents

Advertisement

PST(B) – The advanced range

Overview

Softstarter. Type
Normal start
PST30
In-Line connected
(400 V) kW
15
IEC, Max. A
30
(440-480 V) hp
20
UL, Max FLA
28
400 V, 40 ºC
MCCB (50kA), type
Using MCCB only, type 1
coordination will be achieved.
Fuse protection (65kA), Semiconductor fuses, Bussmann, type
To achieve a type 2 coordina-
tion, semi-conductor fuses
170M1566
must be used.
Switch fuse, type
Suitable switch fuse for re-
commended semi-conductor
OS32GD03P
fuses.
Line contactor, type
The line contactor is not
required for the softstarter
itself but often used to
open if OL trips
Electronic overload relay
Overload protection is used
to protect the motor from
over heating
By-pass contactor, type
The by-pass contactor will
reduce the power loss of the
softstarter. All softstarters
can be operated without
by-pass
A50 ... A300 might be replaced by AF50 ... AF300.
The table above is an overview of possible combinations of devices.
Complete coordination tables are available at
38 Softstarters | 1SFC132005C0201, rev.F
PST30 ... PST72
PST37
PST44
18.5
22
37
44
25
30
34
42
170M1568
AF30
AF38
AF16
AF26
www.abb.com/lowvoltage
PST50
PST60
25
30
50
60
40
40
54
60
T2S160
170M1569
170M1570
OS63GD03P
A50
A63
Built-in
AF30
A40
PST85 ... PST142
PST72
PST85
PST105
37
45
55
72
85
105
50
60
75
68
80
104
170M1571
170M1572
170M3819
OS125GD03P
OS250D03P OS400D03P
A75
A95
A50
PST142
75
142
100
130
T3S250
170M5809
A110
A145
A63
A95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

PssPstbPse

Table of Contents