Overview

Softstarter. Type
Normal start
PSE18
In-line connected
(400 V) kW
7.5
IEC, Max. A
18
(440-480 V) hp
10
18
UL, Max FLA
400 V, 40 ºC
Using MCCB only, type 1
MCCB (35 kA), type
coordination will be achieved
MCCB (50 kA), type
To achieve type 2 coordina-
Fuse protection (85 kA), Semiconductor fuses, Bussmann, type
tion, semi-conductor fuses
must be used
170M1563
Switch fuse, type
Suitable switch fuse for re-
commended semi-conductor
fuses
The line contactor is not
Line contactor, type
required for the softstarter
itself but often used to open
if OL trips
Overload protection is used
Electronic overload relay, type
to protect the motor from
over heating
The by-pass will reduce the
By-pass, type
power loss of the softstarter.
A50 ... A300 might be replaced by AF50 ... AF300
The table above is an overview of possible combinations of devices.
Complete coordination tables are available at
28 Softstarters | 1SFC132005C0201, rev.F
PSE25
PSE30
11
15
25
30
15
20
25
28
170M1564
170M1566
OS32GD03P
AF26
AF30
www.abb.com/lowvoltage
PSE18 ... PSE105
PSE37
PSE45
PSE60
18.5
22
30
37
45
60
25
30
40
34
42
60
T2N160
T2S160
170M1567
170M1568
170M1569
OS63GD03P
AF38
A50
Built-in
Built-in
PSE72
PSE85
37
45
72
85
50
60
68
80
170M1571
170M1572
OS125GD03P
A63
A75
A95
PSE105
55
106
75
104
T3N250
T3S250
170M3819
OS250D03P
A110

Hide quick links: