PSE – The efficient range
Technical data
Cross section of connection cables
Main circuit
Connection clamp
Solid/stranded
Solid/stranded
Tightening torque
(recommended)
Connection bar
Width and thickness
Hole diameter
Tightening torque
(recommended)
Supply and control circuit
Connection clamp
Solid/stranded
Solid/stranded
Tightening torque
(recommended)
Fuse ratings and power losses
Recommended
ABB Overload protection
For
Softstarter
Type
Type
PSE
PSE18
Integrated
PSE25
Integrated
PSE30
Integrated
PSE37
Integrated
PSE45
Integrated
PSE60
Integrated
PSE72
Integrated
PSE85
Integrated
PSE105
Integrated
PSE142
Integrated
PSE170
Integrated
PSE210
Integrated
PSE250
Integrated
PSE300
Integrated
PSE370
Integrated
For the supply circuit 6 A delayed, for MCB use C characteristics.
1)
34 Softstarters | 1SFC132005C0201, rev.F
Type of softstarter
PSE18 ... PSE105
1 x mm
2.5 – 70
2
2 x mm
2.5 – 70
2
Nm
9
mm
mm
Nm
9
1 x mm
2.5
2
2 x mm
1.5
2
Nm
0.5
Max
power loss
Current
at rated I
range
(Internal by-pass)
A
W
5.4-18
0.2
7.5-25
0.4
9-30
0.5
11.1-37
0.8
13.5-45
1.2
18-60
2.2
21.6-72
3.1
25.5-85
4.3
31.8-106
6.6
42.9-143
12.1
51.3-171
17.6
63-210
8.8
75-250
12.5
90.6-302
18
111-370
27.4
PSE142 ... PSE170
17.5
5
ø 8.5
18
2.5
1.5
0.5
Max fuse raiting - main circuit
e
Bussmann Fuses, DIN43 620 (Knife)
A
Type
40
170M1563
50
170M1564
80
170M1566
100
170M1567
125
170M1568
160
170M1569
250
170M1571
315
170M1572
400
170M3819
450
170M5809
500
170M5810
630
170M5812
700
170M5813
800
170M6812
900
170M6813
PSE210 ... PSE370
See accessories
See accessories
See accessories
20
5
ø 10.2
28
2.5
1.5
0.5
1)
Size
000
000
000
000
000
000
000
000
1*
2
2
2
2
3
3
Power
requirements
supply circuit
Holding (VA) /
Pull-in (VA)
16/19.9
16/19.9
16/19.9
16/19.9
16/19.9
16/19.9
16/19.9
16/19.9
16/19.9
16/31
16/31
23/350
23/350
23/350
23/350