60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.
Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch
Table 18. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac
Charger
4.3
5.3
kVA
kVA
kVA
Standard
25
30
40
10A
25
30
40
20A
30
35
40
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
208 Vac
7
10
12.5
18
kVA
kVA
kVA
60
80
110
70
80
125
70
90
125
:
External Bypass Switch Installation
240 Vac
4.3
5.3
7
10
kVA
kVA
kVA
kVA
20
25
35
50
20
30
35
60
25
35
35
60
Rev A www.powerware.com
12.5
18
kVA
kVA
70
100
70
100
80
110