Connecting Power Cables - Huawei BTS3606 Installation Manual

Airbridge cdma base station
Hide thumbs Also See for BTS3606:
Table of Contents

Advertisement

Installation Manual – BTS3606 Cabinet Installation
Airbridge BTS3606&3606A CDMA Base Station
I. Tools
The following tools are required: tape, wire nipper, paper knife, hydraulic pliers,
insulating tapes, soldering iron, and solder wire.
II. Procedure
To prepare power cables, proceed as follows:
1)
According to the cabling route of power cables and grounding cables, measure
the distance from the input port of the lightning arrester to the binding post of the
power distribution box.
2)
Cut cables according to the distance measured. The cables must be a bit longer
than the distance measured so that it will not be too taut when routed.
3)
Cut the insulating cover of each cable head with the paper knife. The length of
the removed cover must be equal to that of the cable lug.
4)
Tighten the lug with hydraulic pliers.
5)
Coat the lug and the naked cable with insulating tape, as shown in Figure 4-11.
Do not expose lugs and naked cables.
(1) The interval is less than 1 mm
(3) The naked stubs are covered with cable caps
Figure 4-11 Preparing lugs

4.3.2 Connecting Power Cables

This section introduces the connecting procedure of various power cables.
I. Connecting –48 V Power Cable (Blue) to the Cabinet
To connect a –48 V power cable to the cabinet, proceed as follows:
1)
Remove the covers on the EMI filter and the power input terminal block by using
a screwdriver.
Huawei Technologies Proprietary
4-15
Chapter 4 Installing Cables
(2) Wrap up with tapes