Transmitter
Wireless Builder display
display
E FAIL*
NVM Fault*
E FAIL*
Program Memory Fault*
E FAIL*
RAM Fault*
The following statuses are displayed only in Wireless Builder Device Status.
blank
Excess Zero Calibration
blank
Excess Span Calibration
blank
Excess Calibrated Range
blank
Calibration Cleared
blank*
Device/Firmware
Mismatch*
Revision 8
November 2010
OneWireless XYR 6000 Pressure Transmitter R120 User's Manual
Definition
Startup diagnostics
detected defect in
Sensor Non-Volatile
Memory
Startup diagnostics
detected defect in
Sensor Read Only
Memory
Startup diagnostics
detected defect in
Processor Random
Access Memory
The selected zero offset
or the lower calibration
trim point is beyond 5%
of the lower end of the
characterized range of
the device.
The calibrated upper and
lower trim has produced
a span that is greater
than 5% of the
characterized span of the
transmitter.
The selected calibration
points used for upper
and lower trim are
outside the characterized
range of the transmitter.
Indicates that both the
upper and lower trim
points as well as the zero
offset has been cleared.
The calibration source is
none.
Sensor Board Firmware
Error. The software did
not pass verification
tests.
5. Operation
5.3. Transmitter PV display
What to do
Replace sensor module. See page
32.
Replace sensor module. See page
32.
Replace sensor module. See page
32.
Clear Calibration
Clear Calibration
Or
Set Factory Calibration
Or
Check the applied trim points and
re-attempt lower and upper (trim)
calibration.
Check that the upper and lower
trim points are both within the
characterized range of the
transmitter and re-attempt upper
and lower (trim) calibration.
Select Factory Calibration
Or
Calibration the zero offset
Or
Calibrate using the lower and
upper trim points.
Replace sensor module. See page
32.