MINIPLEX Transponder Product Selection (Continued)
Audio Expansion Signal Module and Options
Model
Description
Expansion Signal Module; three, 1.5 A Class B
NACs for Audio applications; up to five maximum
4100-5116
per amplifier; NAC rating = 1.5 A, 50 W, or 100
speakers maximum
Expansion Signal Module NAC Expander; NAC
4100-1266
rating = 1.5 A, 50 W, or 100 speakers max.
Expansion Signal Module Class A Adapter; NAC
4100-1267
rating = 1.5 A, 50 W, or 100 speakers max.
Expansion Signal Module Constant Supervision
Adapter; Converts 3 Class B NACs to Constant
4100-1268
Supervision Class B or Class A NACs; for
25 VRMS or 70.7 VRMS audio
General Audio Options
Model
Description
4081-9018
End-of-line resistor harness for 70.7 VRMS NACs; 10 k , 1 W
4100-2320
Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637
Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Initiating Device Circuits (IDCs)
Model
Description
4100-5005
Eight zones, Class B
4100-5015
Eight zones, Class A
Addressable Interface Modules
Model
Description
4100-3101
IDNet Module, 250 point capacity
4100-3104
IDNet Module, 127 point capacity
4100-3105
IDNet Module, 64 point capacity
IDNet Modules, Specifications for each capacity; Module size = 1 Block
Model
Description
®
MAPNET II
Module, 127 point capacity, add devices separately;
4100-3102
Module size = 2 Slots; Loading per MAPNET II device = 1.7 mA
Isolator Module for MAPNET II or IDNet communications; converts one SLC into four
isolated Class A or Class B outputs; up to two Modules can be connected to one SLC;
4100-3103
NOTE: Compatible with MAPNET II Remote Isolators only; for quad isolation with IDNet
Remote Isolators, use 4100-3107 IDNet+ Module (refer to data sheet S4100-0046 for
details)
Relay Modules; Nonpower-Limited
Model
Description
4100-3202
4 DPDT w/feedback
4100-3204
4 DPDT w/feedback
4100-3206
8 SPDT
Current Calculation Notes:
1.
For total supervisory current, add panel module currents to base system value and add all external loads panel-powered loads.
2.
For total alarm current, add panel module currents to base system alarm current and add all panel NAC loads and all external loads
powered from panel power supplies.

General Specifications

Input Power [System (SPS); Expansion (XPS);
Remote (RPS); TrueAlert Power Supplies (TPS);
and 100 W amplifiers]
Power Supply Output
Ratings (System,
Expansion, and Remote
Power Supplies)
Battery capacity range
Battery Charger
(System and Remote
Charger characteristics
Power Supply)
Operating Temp. Range 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Resistive Ratings
10 A
250 VAC
2 A
30 VDC/VAC
3 A
30 VDC/120 VAC
120 VAC Models
220-240 VAC Models
Total Power Supply
9 A total @ nominal 28 VDC, including module currents and
Output Rating
auxiliary power outputs
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
NACs Programmed
2 A maximum per NAC, 5 A maximum @ nominal 28 VDC
for Auxiliary Power
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is UL
listed for up to 110 Ah battery charging for remotely located batteries
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
and performance
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Details and Mounting Reference
Converts one NAC input to three NAC outputs; selects between two
inputs; for Flex-35/50 amplifiers only, two input NACs are required; Single
Block module mounts in expansion bay; Supv = 18 mA; Alarm with 100 W
amplifiers = 52 mA; Alarm with Flex-35/50 amplifiers = 80 mA
Expands module capacity to six, Class B NACs;
Supv = 0.6 mA; Alarm = 60 mA
Converts 3 Class B, NACs to Class A; Supv = 0.6 mA;
Alarm = 30 mA
NAC rating = 1.4 A, 50 W, or 100 speakers max.;
Current vs operating voltage: 25 VRMS Supv = 10 mA;
25 VRMS Alarm = 35 mA; 70.7 VRMS Supv = 38 mA;
70.7 VRMS Alarm = 60 mA
With 250 IDNet devices, add
With 127 IDNet devices, add
With 64 IDNet devices, add
Module without devices
Loading per IDNet device
Module without devices
Fully loaded module, total
Inductive Ratings
10 A
250 VAC
1/2 A
30 VDC/120 VAC
1-1/2 A
30 VDC/120 VAC
3.5 A maximum @ 102 to 132 VAC, 60 Hz
1.75 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
6
These
modules
mount on the
4100-5116;
select one
max. per
4100-5116
as required
Size
Supv.
Alarm
1 Slot
75 mA
195 mA
1 Slot
75 mA
195 mA
Size
Supv.
Alarm
200 mA
250 mA
102 mA
127 mA
51 mA
64 mA
75 mA
115 mA
0.8 mA
1 mA
Size
Supv.
Alarm
270 mA
290 mA
470 mA
490 mA
1 Slot
50 mA
50 mA
Size
Supv.
Alarm
2 Slots
15 mA
175 mA
1 Block
18 mA
70 mA
1 Block
16 mA
200 mA
Output switches to
battery backup
during mains AC
failure or brownout
conditions
S4100-0035-6 4/2005