mc-200 led troubleshooting

Motor
OverLoad
ERD
1. MOTOR OVERLOAD
2. ERD
3. MAX LED
MC-200 LED
Problem Condition
"POWER" LED is OFF
"MATRIX ON-LINE" LED is OFF
"Limit SW ON-LINE" LED is OFF
"MOTOR OVERLOAD" LED is ON
"UL Entrap" LED is ON
"ERD" LED is ON
"EDGE 1" LED is ON
"EDGE 1" LED is flashing
"EDGE 2" LED is ON
"EDGE 2" LED is FLASHING
"PhotoCell" LED is ON
"PhotoCell" LED is FLASHING
"MAX" LED is ON
Example: Inputs 2 & 3
are NOT used and MUST
be jumpered to GND.
12 Volt Power Extension Terminal
12V power for entrapment protection sensor
(see
).
8
ERD
JOG
JOG
Sensitivity
LEFT
RIGHT
5
4
3
MAX
12
16
LED ON
13
15
14
EDGE 1: MONITORED CLOSE ONLY
Edge 2: LEARNED MONITORED OPEN/CLOSE
Photo Cell: LEARNED MONITORED OPEN/CLOSE
4. MATRIX ON-LINE
5. LIMIT SWITCH ON-LINE
Normal
LED
ON
Check if AC POWER ON/OFF SWITCH (on MAX toroid box) is ON.
6
Check if power cable is plugged into back of MC-200 "Power In" input.
ON
Check wiring between Matrix 1 RS485 (+,-, gnd) and MC-200 RS485 (+,-, gnd) terminals. Connect [(+) to
4
(+)], [(-) to (-)] and [GND to GND].
ON
Check if limit switch box is plugged into MC-200 "LIMIT SWITCH" input on back.
1
OFF
Check if gate is binding against catch post or bracket in opened or closed position.
7
Check if gate moves manually with low resistance throughout its full range of motion.
Check if hinges are operational and well greased.
Check if operator is positioned properly relative to the gate hinge, (see
Gate may be too heavy for operator (check manual for maximum gate weight for your model operator).
OFF
An entrapment event has occurred, check an entrapment sensor was triggered (see if ERD, EDGE 1, EDGE 2, or
7
PHOTOCELL LED is on).
OFF
An ERD event may have occurred. Check for gate obstruction.
2
ERD sensitivity is too high for application. Re-adjust ERD setting on MC-200, (see
OFF
Sensor on EDGE 1 input (photocell or edge) may have detected an obstruction while closing the gate.
9
Photocell on EDGE 1 input is misaligned with reflector.
OFF
Sensor on EDGE 1 input (photocell or edge) may not be wired properly, (see
9
Sensor is NOT a N.C. monitored sensor that is UL325 2016 compliant.
Sensor is damaged or malfunctioning.
OFF
Jumper between EDGE 2 and GND is missing or broken (jumper is required if a sensor is not present).
10
Sensor on EDGE 2 input (photocell or edge) may have detected an obstruction while opening or closing the gate.
Photocell on EDGE 2 input is misaligned with reflector.
Sensor is NOT a N.C. monitored sensor that is UL325 2016 compliant.
OFF
Sensor on EDGE 2 input (photocell or edge) may not be wired properly, (see
10
Sensor on EDGE 2 is damaged or malfunctioning.
Sensor is NOT a N.C. monitored sensor that is UL325 2016 compliant.
OFF
Jumper between PHOTOCELL and GND is missing or broken (jumper is required if a sensor is not present).
8
Sensor on PHOTOCELL input (photocell or edge) may have detected an obstruction while opening or closing gate.
OFF
Photocell on PHOTOCELL input is misaligned with reflector.
8
Sensor on PHOTOCELL input (photocell or edge) may not be wired properly, (see
Sensor is NOT a N.C. monitored sensor that is UL325 2016 compliant.
Sensor on PHOTOCELL is damaged or malfunctioning
OFF
MOST sensitive setting for ERD entrapment detection. Select a less sensitive setting (recommend level 10 thru 16)
3
Sensor Wire
Jumper UNUSED Entrapment Inputs
to GND or a fault will occur.
ENTRAPMENT
INPUTS
MATRIX
ON-LINE
Edge
1
1
2 3
2
Limit SW
Edge
Solution(s) for
Problem Condition
16
MC-200
Motor Controller
UL Entrap
POWER
6. POWER
PhotoCell
7. UL ENTRAPMENT
8. PHOTOCELL
9. EDGE 1
10. EDGE 2
).
1
).
10
).
8
).
8
).
8
UL 325 2016 Standard-Megatron Quick Install Rev 10