Enabling Modbus Protocol; Modbus Rtu Parameters And Monitoring Values (M5.8.3); Slave Address; Baud Rate - Vacon 100 Industrial User Manual

Modbus tcp/udp and modbus rtu
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

Fiedlbus parametrization
5.1.2

Enabling Modbus protocol

Modbus TCP/UDP is always enabled in VACON
network settings (IP address etc) before using it. See Chapter 5.3.1.
When using Modbus RTU, you need to enable the protocol. After enabling it, protocol settings will
appear under panel tree P5.8.3.
Parameter name
RS-485 protocol
5.2

Modbus RTU parameters and monitoring values (M5.8.3)

Table 6. Parameters related with Modbus used through RTU
Panel Tree
Parameter
P5.8.3.1.1

Slave address

P5.8.3.1.2

Baud rate

P5.8.3.1.4
Stopbits
P5.8.3.1.3

Parity type

Communication
P5.8.3.1.5
time-out
P5.8.3.1.6 *
Operate Mode
P5.8.3.1.7.1-

IDMap IDs

30
* This feature is not supported in VACON
family AC drives supports only Slave mode. A special application is required for Master functionality.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
®
100 family devices. You need to parametrize the
Table 5. Enabling Modbus RTU protocol
ID
Value
0 = No Protocol
1 = Modbus RTU
2208
2 = BACnet MSTP
3 = N2
Range
Default
1...247
300...230400
1...3
0...2
0...65535
0...1
0...65535
®
100 HVAC. The default application in the VACON
Default
No protocol
ID
Unique slave device
1
2320
address.
Communication speed
300
600
1200
2400
4800
6
2378
9600
19200
38400
57600
76800
115200
230400
1 = 1 stop bit
3
2380
2 = 1.5 stop bits

3 = 2 stop bits

0 = Even
0
2379
1 = Odd
2 = None
Unit is seconds
10
2321
0 = Not used
0 = Slave
0
2374
1 = Master
3130-
0
IDMap IDs
3159
vacon • 23