Logic
Definition
Configuration of
AUX 1
AUX 1 output.
22-23
Configuration of
AUX 2
AUX 2 output.
24-25
Configuration of
AUX 3
AUX 3 output.
26-37
Type of lock.
LOCK
28-29
FIXED CODE
Fixed code
Transmitter pro-
RADIO PROG
gramming

Serial mode

SERIAL MODE
(Identifies how board
is configured in a BFT
network connection).
ADDRESS
Address
Configuration of
EXPI1 input on
EXPI1
input-output expan-
sion board.
1-2
INSTALLATION MANUAL
Cross out
Default
setting
used
0
Output configured as 2nd Radio Channel.
1
Output configured as SCA (gate open light).
3
2
Output configured as Courtesy Light command.
3
Output configured as Zone Light command.
1
4
Output configured as Stair Light
 
5
Output configured as Alarm
6
Output configured as Flashing light
0
7
Output configured as Latch
8
Output configured as Magnetic lock
0
Output configured as 12V
1
Output configured as 12V
0
 
2
Output configured as 24V
3
Output configured as 24V
Receiver is configured for operation in rolling-code mode.
0
Fixed-Code Clones are not accepted.
0
 
Receiver is configured for operation in fixed-code mode.
1
Fixed-Code Clones are accepted.
Disables wireless memorizing of transmitters.
0
Transmitters are memorized only using the relevant Radio menu.
IMPORTANT: Disables the automatic addition of new transmitters, clones and replays.
Enables wireless memorizing of transmitters:
1
 
1- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has already
been memorized in standard mode via the radio menu.
1
2- Press within 10s the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be memorized.
The receiver exits programming mode after 10s: you can use this time to enter other new transmitters.
This mode does not require access to the control panel.
IMPORTANT: Enables the automatic addition of new transmitters, clones and replays.
0
Standard SLAVE: board receives and communicates commands/diagnostics/etc.
0
 
Standard MASTER: board sends activation commands (START, OPEN, CLOSE, PED, STOP) to other
1
boards.
Identifies board address from 0 to 127 in a local BFT network connection.
[ ___ ]
0
 
(see U-LINK OPTIONAL MODULES section)
0
Input configured as Start E command.
1
Input configured as Start I command.
2
Input configured as Open command.
3
Input configured as Close command.
4
Input configured as Ped command.
5
Input configured as Timer command.
6
Input configured as Timer Pedestrian command.
7
Input configured as Phot (photocell) safety.
8
Input configured as Phot op safety (photocell active during opening only).
1
 
9
Input configured as Phot cl safety (photocell active during closing only).
10
Input configured as Bar safety (safety edge).
Input configured as Phot test safety (tested photocell).
11
Input 3 (EXPI2) on input/output expansion board is switched automatically to safety device test
input, EXPFAULT1.
Input configured as Phot op test safety (tested photocell active during opening only).
12
Input 3 (EXPI2) on input/output expansion board is switched automatically to safety device test
input, EXPFAULT1.
Input configured as Phot cl test safety (tested photocell active during closing only).
13
Input 3 (EXPI2) on input/output expansion board is switched automatically to
safety device test input, EXPFAULT1.
Input configured as Bar safety (tested safety edge).
14
Input 3 (EXPI2) on input/output expansion board is switched automatically to
safety device test input, EXPFAULT1.
Optional extras
solenoid latch.
magnetic lock.
solenoid latch.
magnetic lock.
37
THALIA P