Oven Functions - Siemens Maxum II Reference Manual

Hide thumbs Also See for Maxum II:
Table of Contents

Advertisement

Electronic Compartment Component Descriptions and Maintenance Procedures
2.2 Power Entry and Control Module
Additional Relay Outputs
Relay circuits LWH5 and LWH6 when used for purposes other than on/off control of low
wattage heaters can supply four separate outputs. A simple jumper on pins 1 to 2 on output
connector TB7 or TB8 makes this possible. With the jumper in place, each connector will
provide two independent outputs; see the diagram below.
Solid
State
Relay
Figure 2-8
2.2.3.5

Oven Functions

Temperature Monitoring and Control
The PECM_CTL board has two temperature monitor and control channels for use with the high-
wattage heaters (HWH). Each channel includes;
● RTD input
● Mounting location and connector for
setpoint module
● Comparator circuit
● PWM control signal output
The HWH control path is shown below.
24
Relay AC Supply Voltage
TB7 (LWH5)
or
TB8 (MWH)
LW5 & LW6 Relay Circuit Jumper Connections
Heater
A&B Common
Unused
AC Hot
SSRA Hot
AC Neutral A
Unused
SSRB Hot
To LWH Hot Load SSRB Load Hot
AC Neutral B
To LWH Neutral
● Control input (can accept an external
control signal from another module if
desired)
● Control output for HWH SSR module
● AC power output for HWH SSR
Usage
Sample
System Relays
SSRA Load Hot
SSRA Load Neutral
SSRB Load Neutral